Operation and configuration
35
CMD420_421-DM_D00224_01_M_XXEN/08.2016
5.5.6
Set the 100-% reference for the analogue interface
Set here whether the 100% value of the output signal is to be related to the
response value I2 () (AL) or to a freely configurable value.
Factory setting = value related to the highest freely configurable current of
L1, L2 or L3 with 0.30 A (CMD420-DM) resp. 1.5 A (CMD421-DM).
The freely configurable values for CMD420-DM are between 0.1 and 1 A,
for CMD421-DM between 0.5 and 5 A.
The following example shows how the 100%-reference value is changed
from the freely configurable highest current value, predefined for L1, L2 or L3
to response value AL.
By activating (on) the menu item "> L1L2L3 I2 AL", the previously activated
menu item "> L1L2L3 I 0.30 A" will automatically be deactivated.
For additional information, refer to "Chapter 3.2.9 Menu item AnA for inter-
face configuration".
3x
>1,5 s
2x