6.9 Indication of device and measuring errors
The following table explains the error messages that may occur.
6.10 Factory settings EDS195P (state as supplied)
Most of the settings are made on the menu. If this is not the case, the setting is marked with
(button).
Operating mode (button):
I
Δ
L
(EDS mode = insulation fault location)
Current transformer (button):
Measuring clamp PSA3052 (for EDS3090 and 3096)
Measuring clamp PSA3352 (for EDS3091)
Illumination (button):
Off
Fault memory:
On
Buzzer: On
Response value
I
Δ
L
with PSA30…:
5 mA
Response value
I
Δ
L
with PSA33…:
0.5 mA
Response value
I
Δ
n
:
100 mA
System frequency
I
Δ
n
:
50 Hz
Measurement of harmonics
I
Δ
n
:
Off
User interface language:
English
Time:
CET
Can only occur after the end of the self-test:
- Incorrect current transformer type set
- During the self-test the clamp was:
Not stationary
Or a residual current was flowing through it
Or the PGH locating current was flowing through it
- EDS195P hardware faulty
Press the "RESET" button to restart a self test.
No measuring clamp or no measuring current transformer on
the measuring input or incorrect transformer type connected
Measures:
Connect correct measuring clamp or correct measuring current
transformer
A permanent display of pause (- - -) indicates no measurement is
possible.
Steps:
- Hold the measuring clamp still
- Avoid low frequency residual currents
A malfunction has occurred during insulation fault location
Possible causes:
- The measuring clamp was not held still.
- There is a low frequency residual current flowing through the
measuring clamp that is interfering with the EDS measurement
- There a magnetic field around the measuring clamp that is
interfering with the EDS measurement
- EDS195P hardware faulty
If the EDS195 can no longer detect the locating current due to system interfer-
ence and an existing alarm is therefore cleared, an insulation fault will be detect-
ed again at the end of the interference.
Self test error
PRESS ->RESET
M
PSA30xx
No CT connected
M
PSA30xx
I
L
= mA
Anspr. = 5mA
M
PSA30xx
Error I
Δ
L
M
PSA30xx
Summary of Contents for EDS3090
Page 6: ...Table of Contents 6 EDS309x_D00012_03_M_XXEN 11 2014...
Page 26: ...Considerations prior to use 26 EDS309x_D00012_03_M_XXEN 11 2014...
Page 62: ...Frequently Asked Questions 62 EDS309x_D00012_03_M_XXEN 11 2014...
Page 65: ......
Page 66: ......
Page 67: ......