Important information
39
isoHV425_D00082_03_M_XXEN/05.2020
RW = Read/Write; RO = Read only; WO = Write only
3020
RW
Delay on release "toff" for relays
K1 and K2
Uint16
s
0 … 99
3021
RW
Repetition time "test" for auto-
matic device test
Uint16
–––
0 = OFF
1 = 1 h
2 = 24 h
3022
RW
Reserved
–––
–––
–––
3023
RW
Reserved
–––
–––
–––
3024
RW
Check system connection during
device test 'nEt'
Uint16
–––
0 = Inactive
1 = Active
3025
RW
Device test during device start "S.
Ct"
Uint16
–––
0 = Inactive
1 = Active
3026
RW
Request stop mode (0 = deacti-
vate device)
Uint16
–––
0 = Stop
1 = ---
3027
RW
Signalling assignment of relay 1
"r1"
Uint16
–––
Bit 9 … Bit 1
3028
RW
Signalling assignment of relay 2
"r2"
Uint16
–––
Bit 9 … Bit 1
8003
WO
Factory settings for all parameters Uint16
–––
0x6661 "fa"
8004
WO
Factory settings only for parame-
ters resettable by FAC
Uint16
–––
0x4653 "FS"
8005
WO
Start device test
Uint16
–––
0x5445 "TE"
8006
WO
Clear fault memory
Uint16
–––
0x434C "CL"
9800
…9809
RO
Device names
Uint16
(ASCII)
–––
–––
9820
RO
Software ID number
Uint16
–––
Software ID
9821
RO
Software version number
Uint16
–––
Software ver-
sion
9822
RO
Software version: Year
Uint16
9823
RO
Software version: Month
Uint16
9824
RO
Software version: Day
Uint16
9825
RO
Modbus driver version
Uint16
Register
Mode
Description
Format
Unit
Value range