Important information
29
isoHV425_D00082_03_M_XXEN/05.2020
5.3 "AL" menu – response value setting
The two parameters "R1" and "R2" for monitoring the insulation resistance
R
F
can be
found in the response value menu "AL". The value "R1" can only be set higher than the
value "R2". If the insulation resistance
R
F
reaches or falls below the values "R1" or "R2",
this leads to an alarm message. If
R
F
exceeds the values "R1" or "R2" plus the hysteresis
value (see table below), the alarm will be cleared.
Also in the response value menu "AL" the parameters ("U <" and "U >") for monitoring
the system voltage
U
n
can be activated or deactivated.The maximum undervoltage val-
ue is limited by the overvoltage value.
FAC
= Factory setting;
Cs
= Customer settings
5.4 "out" menu
5.4.1
Configuration of the relay operating mode
FAC
= Factory setting;
Cs
= Customer settings
Display
Activation
Setting value
Description
FAC
Cs
Value range
FAC
Cs
R1 <
on
R2 … 500
50
kΩ
Prewarning value
R
an1
Hys. = 25 %/min. 1 kΩ
R2 <
on
10… R1
25 kΩ
Alarm value
R
an2
Hys. = 25 %/min. 1 kΩ
U <
off
30 … U>
30 V
Alarm value undervoltage RMS
Hys . = 5 %/min. 5 V
U >
off
U< … 1.10k
1100 V
Alarm value overvoltage RMS
Hys. = 5 %/min. 5 V
Relay K1
Relay K2
Description
Display
FAC
Cs
Display
FAC
Cs
n.c.
n.c.
Operating mode of the relay n.c/n.o.
1
2