RCMS460-490_D00067_00_Q_XXDE / 03.2021 7
LINETRAXX® RCMS460-D/-L, RCMS490-D/-L
Technische Daten
a) RCMS4
…
-D1
Versorgungsspannung
U
S
..............................................DC 24…75 V
............................................................ AC 24…60 V (AC/DC ±20 %)
Frequenz der Versorgungsspannung ............................DC, 50/60 Hz
Bemessungsspannung .............................................................
100 V
Bemessungs-Stoßspannung/Verschmutzungsgrad ............
2,5 kV/3
Überspannungskategorie ................................................................III
Sichere Trennung (verstärkte Isolation) zwischen. ..............A1, A2) -
................................................................(k1, l…k12, R, T/R, T, A, B)
Spannungsprüfung nach IEC 61010-1 ..................................1,344 kV
Bemessungsspannung .............................................................
250 V
Bemessungs-Stoßspannung/ Verschmutzungsgrad ...............
4 kV/3
Überspannungskategorie ............................................................... III
Basisisolierung zwischen ...... (A1, A2), (k1, l…k12, R, T/R, T, A, B) -
........................................................(C11, C12, C14), (C21, C22, C24),
..................................................... (11,14), (21,24), (31,34), (41,44),
......................................................(51,54), (61,64), (71,74), (81,84),
............................................(91,94),(101,104), (111,114), (121,124)
Basisisolierung zwischen ...................................................................
................ (11, 14) - (21, 24) - (31, 34) - (41, 44) - (51, 54) - (61, 64)
Spannungsprüfung nach IEC 61010-1 ....................................2,21 kV
Bemessungsspannung .............................................................
250 V
Bemessungs-Stoßspannung/Verschmutzungsgrad ................
6 kV/3
Überspannungskategorie ................................................................III
Sichere Trennung (verstärkte Isolation) zwischen .............................
..................................................... (C11, C12, C14) - (C21, C22, C24) -
..............................(11, 14, 21, 24, 31, 34) - (41, 44, 51, 54, 61, 64) -
..........(71,74) - (81,84) - (91,94) - (101,104) - (111,114) - (121,124)
Spannungsprüfung nach IEC 61010-1 ..................................3,536 kV
b) RCMS4
…
-D2
Versorgungsspannung
U
S
..........AC/DC 100…240 V (-20…+15 %)
Frequenz der Versorgungsspannung .............................DC, 50/60 Hz
Bemessungsspannung ............................................................
250 V
Bemessungs-Stoßspannung/Verschmutzungsgrad ................
6 kV/3
Überspannungskategorie ................................................................III
Sichere Trennung (verstärkte Isolation) zwischen ..............(A1, A2) -
...............................................................(k1, l…k12, R, T/R, T, A, B),
........................................................(C11, C12, C14), (C21, C22, C24),
.........................................(11,14), (21,24), (31,34), (41,44), (51,54),
......................................................(61,64), (71,74), (81,84), (91,94),
.........................................................(101,104), (111,114), (121,124)
Sichere Trennung (verstärkte Isolation) zwischen
.................................................... (C11, C12, C14) - (C21, C22, C24) -
..............................(11, 14, 21, 24, 31, 34) - (41, 44, 51, 54, 61, 64) -
................................................................(71,74) - (81,84) - (91,94) -
......................................................(101,104) - (111,114) - (121,124)
Spannungsprüfung nach IEC 61010-1 ..................................3,536 kV
Technical data
a)RCMS4
…
-D1
Supply voltage
U
S
..........................................................DC 24…75 V
..............................................................AC 24…60 V (AC/DC ±20 %
Supply voltage frequency .............................................DC, 50/60 Hz
Rated insulation voltage .........................................................
100 V
Rated impulse voltage/pollution degree ...........................
2.5 kV/3
Overvoltage category .....................................................................III
Protective separation (reinforced insulation) between ...... (A1, A2) -
................................................................(k1, l…k12, R, T/R, T, A, B)
Voltage test acc. to IEC 61010-1 ..........................................1.344 kV
Rated insulation voltage .........................................................
250 V
Rated impulse voltage/pollution degree ...............................
4 kV/3
Overvoltage category ......................................................................III
Basic insulation between ...... (A1, A2), (k1, l…k12, R, T/R, T, A, B) -
........................................................(C11, C12, C14), (C21, C22, C24),
......................................................(11,14), (21,24), (31,34), (41,44),
......................................................(51,54), (61,64), (71,74), (81,84),
............................................(91,94),(101,104), (111,114), (121,124)
Basic insulation between ...................................................................
................ (11, 14) - (21, 24) - (31, 34) - (41, 44) - (51, 54) - (61, 64)
Voltage test acc. to IEC 61010-1 ............................................2.21 kV
Rated insulation voltage .........................................................
250 V
Rated impulse voltage/pollution degree ...............................
6 kV/3
Overvoltage category ......................................................................III
Protective separation (reinforced insulation) between ......................
..................................................... (C11, C12, C14) - (C21, C22, C24) -
..............................(11, 14, 21, 24, 31, 34) - (41, 44, 51, 54, 61, 64) -
..........(71,74) - (81,84) - (91,94) - (101,104) - (111,114) - (121,124)
Voltage test acc. to IEC 61010-1 ..........................................3.536 kV
b) RCMS4
…
-D2
Supply voltage
U
S
..................... AC/DC 100…240 V (-20…+15 %)
Supply voltage frequency ..............................................DC, 50/60 Hz
Rated insulation voltage ..........................................................
250 V
Rated impulse voltage/pollution degree ................................
6 kV/3
Overvoltage category ......................................................................III
Protective separation (reinforced insulation) between ...... (A1, A2) -
...............................................................(k1, l…k12, R, T/R, T, A, B),
........................................................(C11, C12, C14), (C21, C22, C24),
.........................................(11,14), (21,24), (31,34), (41,44), (51,54),
.......................................................(61,64), (71,74), (81,84),(91,94),
.........................................................(101,104), (111,114), (121,124)
Protective separation (reinforced insulation) between
.................................................... (C11, C12, C14) - (C21, C22, C24) -
..............................(11, 14, 21, 24, 31, 34) - (41, 44, 51, 54, 61, 64) -
................................................................(71,74) - (81,84) - (91,94) -
......................................................(101,104) - (111,114) - (121,124)
Voltage test acc. to IEC 61010-1 ......................................... 3.536 kV