The boiler must be positioned so that a plug socket (400V / 50Hz) is always accessible.
•
The boiler is connected to the mains with a fixed and flexible power supply cord with standardized plug.
•
Protection against electric shock must be made in accordance with valid
Č
SN EN standard (see chap.
5.1.)
Boiler placement with regard to fire regulations:
1. Positioning on a floor made of incombustible material
•
Place the boiler on an incombustible thermally insulating pad exceeding the boiler floor plan on all
sides by 20 mm.
•
If the boiler is located in the basement, it is advisable to place it on a substructure at least 50 mm
high. The boiler must stand horizontally so any unevenness of the substructure must be eliminated
by screwing or unscrewing the foot of the fuel container beneath the fuel screw feeder.
2. Safe distance from flammable materials
•
The minimum allowable distance of the outer contours of the boiler and flue gas ducting from
flammable materials (see detailed specifications in
Č
SN EN 13 501-1+A1:2010) during installation
and operation of the boiler must be at least 400 mm.
Boiler positioning with regard to the necessary handling space:
•
Basic environment AA5 / AB5 according to
Č
SN 33 2000-1 ed.2:2009
•
The handling space left in front of the boiler must be at least 1000 mm
•
Minimum distance between the rear part of the boiler and the wall must be 500 mm
•
The gap on the side of the fuel container must be at least 500 mm
•
The gap on the side of the boiler body must be at least 500 mm for the possibility to clean the convective
area of the heat exchanger and connection of the ash remover
•
The gap above the fuel container must be at least 1000 mm (for BENEKOV S16 and S26 boilers) and
1400 mm (for BENEKOV S51 boiler) to allow full opening of the fuel tank cover.
Fig. No. 20 Placement of the boiler in the boiler room
Boiler positioning with regard to the chimney:
Summary of Contents for S16
Page 1: ...BOILER OPERATING AND INSTALLATION INSTRUCTION MANUAL BENEKOV S16 BENEKOV S26 BENEKOV S51 ...
Page 20: ...20 Fig no 14 Boiler ash remover for S51 Fig no 15 Boiler flue gas exhaust for S16 and S26 ...
Page 27: ...27 Fig no 22 Connection dimensions of BENEKOV S26 boiler ...
Page 28: ...28 Fig no 23 Connection dimensions of BENEKOV S51 boiler ...