25
•
The BENEKOV S16 and S26 boiler is connected to the chimney using a metal pipe with a diameter of
145 or 150 mm.
•
The BENEKOV S51 boiler is connected to the chimney using a metal pipe with a diameter of 200 mm.
Fuel placement:
•
Pellets are recommended to be stored in their original packaging from the manufacturer (PET bags or
"big bags") in a dry place.
•
Do not store fuel behind the boiler or store it next to the boiler within a distance shorter than 400 mm.
•
The manufacturer recommends keeping the min. distance between the boiler and fuel at 1000 mm or to
store the fuel in a different room away from the boiler.
The room where the boiler is installed must be provided with permanent intake and outlet of air for
combustion and ventilation. Air consumption of:
- BENEKOV S16 at nominal output is about 45 m
3
. h
-1
- BENEKOV S26 at nominal output is about 75 m
3
. h
-1
- BENEKOV S51 at nominal output is about 150 m
3
. h
-1
According to regulations, an authorized person must perform the connection of the heating system pipeline
or heater heating element pipeline.
NOTE:
When connecting the boiler to the heating system the lowest point as close to the
boiler as possible must be equipped with a drain tap.
6. Commissioning of the boiler - instructions for contracted service
organizations
Commissioning can only be performed by a contracted service organization authorized to conduct
this activity.
6.1. Electric connection using via connectors
In the course of putting the boiler into operation there is no need to tamper with any electrical connection of
the boiler’s control unit. Wiring of electrical components of the boiler and peripheral devices (e.g. ash
remover, automatic ignition, etc.) is via the connectors, which allows for quick and easy disconnection from
(or connection to) the boiler control unit.
Depending on the variant and equipment the boiler may be fitted with connectors marked with the following
symbols:
- Fuel feed drive connector
- Fan connector
- Automatic ignition connector
- Ash remover connector
Summary of Contents for S16
Page 1: ...BOILER OPERATING AND INSTALLATION INSTRUCTION MANUAL BENEKOV S16 BENEKOV S26 BENEKOV S51 ...
Page 20: ...20 Fig no 14 Boiler ash remover for S51 Fig no 15 Boiler flue gas exhaust for S16 and S26 ...
Page 27: ...27 Fig no 22 Connection dimensions of BENEKOV S26 boiler ...
Page 28: ...28 Fig no 23 Connection dimensions of BENEKOV S51 boiler ...