background image

26

8.4.2) LOGICS (

LOG

)

MENU

FUNZIONE

ON-OFF-(Default)

MEMO

TCA

Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled

(ON)

IbL

Enables or disables condominium function. 
On: condominium function enabled. The step-by-step impulse or transmitter impulse has no 
effect during the opening phase.
Off: condominium function disabled. 

(OFF)

ibca

The multi-flat function is enabled or disabled during the TCA counting. 
On: the bloc of flat function is enabled. The Step-by-Step signal or the transmitter signal has no 
effect during the TCA counting.
Off: the bloc of flat function is disabled.

(OFF)

SCL

The rapid closure is enabled or disabled
On: rapid closure is enabled. When the gate is open or moving, the photocell activation causes 
the automatic closure of the gate after 3 s. It is activated only with 

TCA

:ON 

Off: rapid closure is disabled. 

(OFF)

PP

Selects the operating mode of the ”Step by step button” and of the transmitter.
On: Operation: OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >

(OFF)

PRE

Enables or disables pre-blinking.
On: Pre-blinking enabled. Blinking is activated 3s before the motor starts.
Off: Pre-blinking disabled.

(OFF)

htr

Enabled or disables HOLD-TO-RUN function
On: HOLD-TO-RUN function.
The pressure of the OPENS/CLOSES button must be maintained throughout the entire manoeuvre. 
The opening of the STOP input stops the motor. All the safety inputs are deactivated.
Off: Automatic/semiautomatic function

(OFF)

opcl

PP input as OPEN and PED input as CLOSED are enabled or disabled.
On: PP input is enabled as OPEN and PED input is enabled as CLOSE.
Off: PP and PED inputs are enabled with their function.

(OFF)

ltca

Selects the operating mode of the blinking light during the time TCA
On: Blinking light on during TCA
Off: Blinking light off during TCA

(OFF)

phcl

The operating mode of the PHOT C input is selected.
On: PHOT C input is activated in both opening and closing phases.
In the opening phase: the contact opening causes the motor stop. When the photocell is 
released, the motor restarts in the opening phase.
In closing phase: the contact opening causes the motor stop. When the photocell is released, 
the motor inverts the movement direction (open).
Off: The PHOT C input is activated in the closing phase only.
In the closing phase: the contact opening causes the motor stop and the immediate reversion 
of the operation direction (open).

(OFF)

TST1

Enables or disables checking of photocells on PHOT input, active both in closing and in opening.
On: Check enabled. If the check has a negative result, no manoeuvre is commanded. See 
Fig.167- “PHOTO TEST”. (AUX1=3)
Off: Check of photocells each time a manoeuvre is disabled. This setting requires maintenance 
of photocells every 6 months.

(OFF)

tst2

Enables or disables the check of photocells on PHOT C input.
On: Check enabled. If the check fails, no manoeuvre will be enabled. (AUX1=3)
Off: Check of photocells each time a manoeuvre is disabled. This setting requires maintenance 
of photocells every 6 months.

(OFF)

TSTm

Enables or disables motors check.
On: Check enabled. If the check has a negative result, no manoeuvre is commanded. 
Off: Check disabled. 

(OFF)

bar

Changing the operating mode of the PHOT OPEN and BAR inputs in the event the sensitive 
edges are installed on the mobile opening and closure edges (see Fig.21).
On: The PHOT OPEN input assumes a similar function to the BAR input, but inverts motion for 
3s only during the opening phase. The edge connected to the BAR input is only active during 
the closure phase.
Off: Intervention of the sensitive edge connected to the BAR input stops movement of the door 
and inverts for approx. 3s, both opening and closure. 
The PHOT OPEN input re-starts functioning of the photocell active on opening.

(OFF)

aopf

The “forced opening in case of power cut-off” function is activated or deactivated (it can be 
activated only with connected and operating emergency batteries). 
On: Activated function. In the event of power failure, before the emergency battery completely 
discharged, the control unit causes an opening operation.
The barrier remains open until the power supply is back.
Off: Deactivated function.

(OFF)

Summary of Contents for BULL 1524

Page 1: ...L8543219 05 2018 rev 3 BULL 1524 BULL 1524 S UNIONE NAZIONALE COSTRUTTORI AUTOMATISMI PER CANCELLI PORTE SERRANDE ED AFFINI IT EN DE FR ES PL ...

Page 2: ...2 A B 1 200 245 316 340 300 215 340 34mm BULL PI Optional 40 3 1 8 2 0 4 7 0 1 8 0 2 3 ...

Page 3: ...3 V Z R 4 7 B F T MIN 10 mm MAX 20 mm MIN 120 mm MAX 140 mm 5 6 R D R D ...

Page 4: ...4 8 1 mm 9 P S M C 10 A OK F 1 3 cm S 11 B C A K Max 35 mm X K X 3 mm 74 mm 35 mm 63 mm BULL 1524S optional MLS ...

Page 5: ...5 12 13 14 C L 7 4 1 2 3 POWER 2 x 1 5 RG 58 5 4 x 0 25 4 6 5 2 x 0 25 3 x 0 25 15 ...

Page 6: ... PED P P MOT AUX1 BAR ANT M LAMP 24Vdc 24Vdc 500 mA 24V RADIO BLINK AUX2 J3 COM SWO SWC STOP PHOTC PHOTO SHLD ANT PED P P U5 F1 MOT AUX1 BAR 24V CP B1524 BAT BAT 2xDA BT6 Optional L N F1 SA 24V SIS Optional Advantouch LED 2 LED 1 M1 M2 M3 2xDA BT6 Optional J3 Open DAS N C J3 Close DAS 8K2 C1 ...

Page 7: ...2 24Vdc AUX1 SERVICE LIGHT L N 230Vac LAMP 24Vac LAMP AUX1 II CH RADIO AUX1 0001 Relè 24Vdc CH2 TX 24Vac 24Vac COM NC NO RX TX COM AUX2 PHOTO 24Vdc 24Vdc AUX2 AUX2 0003 tst1 on SCA PHOTOTEST PHOTO PHOTOTEST PHOTC AUX2 0000 AUX2 0002 AUX2 24Vdc SERVICE LIGHT L N 230Vac LAMP 24Vac LAMP Relè 24Vdc 24Vac 24Vac COM NC NO RX TX COM AUX2 PHOTC 24Vdc AUX2 0003 tst2 on AUX1 II CH RADIO AUX2 0001 CH2 TX AUX...

Page 8: ... B A MASTER Menu BUS ID 0 SLAVE Menu BUS ID 1 3x0 5mm 20 OPEN Open Safety Edge COM PHOTO Close Safety Edge 8K2 N O Jumper BAR BAR MOTOR J3 Open BAR N C J3 Close BAR 8K2 N C 21 bar On 19 OPEN OPEN OPEN OPEN MINV Off MINV On ...

Page 9: ...9 22 DA BT6 ...

Page 10: ...c pso psc 40 50 99 99 50 sldc 20 20 20 20 20 20 TLS 60 aux1 0 aux2 1 50 TCA PAR radi Power ON Display OFF Firmware Ver 3s Diagnostic TCA htr opcl ltca phcl tst1 tst2 opcl bar aopf minv rem Schema menu di programmazione Menu programming layout Diagramm Programmiermenü Menu de programmation Menú de la carta de programación Układ menu programowania ...

Page 11: ...en Appuyez sur la touche Presionar la tecla Wcisnąć przycisk Selezionare il valore desiderato con i pulsanti e Increase decrease the value with keys and Mit den Tasten und kann man eingerichtete Werte ändern Régler la valeur désirée avec les touches et Establecer con las teclas y el valor deseado Nastawia przyciskami i obraną wartoś Premere il tasto PG Press key PG Die Taste PG drücken Appuyez sur...

Page 12: ...raining by persons responsible for their safety Apply all safety devices photocells safety edges etc required to keep the area free of impact crush ing dragging and shearing hazard Bear in mind the standards and directives in force Good Practice criteria intended use the installation environment the operating logic of the system and forces generated by the automated system Installation must be car...

Page 13: ...travel during opening closing is limited by sturdy mechanical stops QUICK PROGRAMMING NOTE Quick programming conditions Transmitter memory empty Autoset never run previously Only valid with ARC Advanced Rolling Code transmitters If you make a mistake during the quick programming procedure you can disconnect the power supply and restart the procedure Quick programming steps 1 Unlock the gate manual...

Page 14: ...he screws V making sure once the actuator has been installed that between rack and the drive gear there is always approx 1mm clearance see Fig 9 to get this clearance use the slots on the rack 5 MANUAL OPERATION FIG 12 13 14 In the event of power failure or malfunction to manually operate the gate proceed as follows After inserting the customized key C turn it anti clockwise and pull the lever L o...

Page 15: ...ment is stopped and reversed for about 3s If the edge is not in use DAS Jumper open BAR terminals are short circuited AUX 1 Auxiliary output AUX 1 Output with N O contact configurable by means of the logic AUX 1 24V 24 Vdc Accessory power supply 24Vdc 500 mA maximum MOT Motor Motor connection 24Vdc N A Not used 8 2 PROGRAMMING The programming of the various functions of the control unit is carried...

Page 16: ... the opening phase 1 99 20 PMC Adjusts the motor torque applied to sliding door during the closing phase 1 99 20 PSO Adjusts the motor torque applied to sliding door during the slowdown in opening phase Fig 9 Slow Open 1 99 20 PSC Adjusts the motor torque applied to sliding door during the slowdown in closing phase Fig 10 Slow Close 1 99 20 tls Activation time of the courtesy light contact Value e...

Page 17: ...g causes the motor stop When the photocell is released the motor restarts in the opening phase In closing phase the contact opening causes the motor stop When the photocell is released the motor inverts the movement direction open Off The PHOT C input is activated in the closing phase only In the closing phase the contact opening causes the motor stop and the immediate reversion of the operation d...

Page 18: ...he second time it shows the last 4 Example PG 0012 PG 3456 made 123 456 cycles 8 4 5 MAINTENANCE CYCLES maci This function enables to activate the maintenance request notice after a number of manoeuvres determined by the installer To activate and select the number of manoeuvres proceed as follows Press button PG the display will show OFF which indicated that the function is disabled default value ...

Page 19: ...nector as shown in Fig 16 Each SIS unit must be connected to the other one by means of 3 wires by 0 5 sq mm each as shown in Fig 20 One of the control unit must be set as MASTER ID 0 and the other one as SLAVE ID 0 All the commands commands given by transmitters push buttons or safety devices received by the MASTER sliding door are sent to the SLAVE sliding door which will replicate instantaneousl...

Page 20: ...ption of operation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Date _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Engineer s Signature...

Page 21: ...rate hazards due to wear and tear The operator is maintenance free but it is necessary to check periodically if the safety devices and the other components of the automation system work properly Wear and tear of some components could cause dangers Keep the maintenance record that must be handed to you by the installer and comply with the maintenance schedule Unplug the system from the power source...

Page 22: ...72 4 5 6 7 8 9 10 11 1 2 3 12 BULL 1524 BULL 1524 S Ref Code Note Ref Code Note 1 9686327 7 9686032 2 9686328 8 9688346 3 9686329 9 9686337 4 9686333 10 9686331 5 9686341 11 9688347 6 9686335 12 9688102 ...

Page 23: ...original available from the manufacturer Benincà Luigi Legal Officer Sandrigo 29 05 2018 EG Konformitätserklärung DoC Name des Herstellers Automatismi Benincà SpA Adresse Via Capitello 45 36066 Sandrigo VI Italia Telefon 39 0444 751030 E Mail Adresse sales beninca it Zur Erstellung der technischen Dokumentation berechtigte Person Automatismi Benincà SpA Erklärt dass das Dokument unter alleiniger V...

Page 24: ...AUTOMATISMI BENINCÀ SpA Via Capitello 45 36066 Sandrigo VI ITALY Tel 0444 751030 r a Fax 0444 759728 www beninca com sales beninca it ...

Reviews: