14.2) PARAMETERS (

PAR

)

MENU

FUNCTION

MIN-MAX-(Default)

MEMO

TCA

Automatic closing time. Enabled only with logic “TCA”=ON.
At the end of the set time, the control unit commands a closing maneuver .

1-240-(20s) 

FSTS

Adjusts the opening and closing speed of the barrier (standard speed, before the slowdown phase).

50-99-(99)

sldo

Adjusts the slowdown speed of the barrier during the opening phase* (Fig.8 -slow Open).

20-70-(50)

sldc

Adjusts the slowdown speed of the barrier during the closing phase * (Fig.8 -slow Close).

20-70-(50)

tsmo

Sets the starting point of the slowdown during the opening phase (Fig.8-  beginning of the slow 
Open). The value is expressed in seconds.

1-99-(20)

tsmc

Sets the starting point of the slowdown during the closing phase (Fig.8- beginning of the slow 
Close). The value is expressed in seconds.

1-99-(20)

PMO

Adjusts the motor torque applied to the barrier during the opening phase.*

1-99-(20)

PMC

Adjusts the motor torque applied to the barrier during the closing phase.*

1-99-(20)

PSO

Adjusts the motor torque applied to the barrier during the slowdown in opening phase * (Fig.8 
- Slow Open).

1-99-(20)

PSC

Adjusts the motor torque applied to the barrier during the slowdown in closing phase * (Fig.8- 
Slow Close).

1-99-(20)

SeaU

Not used

SEAR

Not used

tls

Activation time of the courtesy light contact. Value expressed in seconds. At the beginning of 
each maneuver the contact latches for the set time.
See the description of AUX1 parameter.

1-240 (60)

saso

Sets a short reversion after reaching the limit switch in open position. Can be useful for facilitat-
ing the manual release.

0-5 (0)

sasc

Sets a short reversion after reaching the limit switch in close position. Can be useful for facilitat-
ing the manual release.

0-5 (0)

aux1

Selects the functioning mode of the auxiliary output 1 (N.O. clean contact)
0: Open barrier light, close contact when the barrier is open, open contact when the barrier is 
close, intermittent during the maneuver (fig. 11, SCA)
1: Second radio cannel of the built in receiver
2: Boom light, for controlling the LED light installed on the BOOM, see also the parameter LBAR.
3: Courtesy light, the contact remains close according to the parameter TLS (fig.11 SERVICE 
LIGHT) 
4: Photocells test, see wiring diagram in Fig.11 (PHOTOTEST)
5: Close contact with open barrier
6: Close contact with close barrier

0-6-(0)

aux2

Selects the functioning mode of the auxiliary output 1 (N.O. clean contact)
0: Open barrier light, close contact when the barrier is open, open contact when the barrier is 
close, intermittent during the maneuver (fig. 15, SCA)
1: Second radio cannel of the built in receiver
2: Boom light, for controlling the LED light installed on the BOOM (EVA.LED), see also the parameter LBAR.
3: Courtesy light, the contact remains close according to the parameter TLS (fig.15 SERVICE LIGHT) 
4: Photocells test, see wiring diagram in Fig.15 (PHOTOTEST)
5: Close contact with open barrier
6: Close contact with close barrier
7: Maintenance warning light. The contact closes when the number of manoeuvres set in the 
Maintenance Cycle menu is reached (MACI).

0-6-(2)

* ATTENTION: A WRONG SETTING OF THESE PARAMETERS CAN BE DANGEROUS. 
RESPECT THE REGULATION IN FORCE!

14.3) LOGICS (

LOG

)

MENU

FUNZIONE

ON-OFF-(Default)

MEMO

TCA

Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled

(ON)

IbL

Enables or disables condominium function. 
On: condominium function enabled. The step-by-step impulse or transmitter impulse has no 
effect during the opening phase.
Off: condominium function disabled. 

(OFF)

ibca

The multi-flat function is enabled or disabled during the TCA counting. 
On: the bloc of flat function is enabled. The Step-by-Step signal or the transmitter signal has no 
effect during the TCA counting.
Off: the bloc of flat function is disabled.

(OFF)

Summary of Contents for VE.650

Page 1: ...L854200192 07 2020 rev 1 VE 650 UNIONE NAZIONALE COSTRUTTORI AUTOMATISMI PER CANCELLI PORTE SERRANDE ED AFFINI IT EN DE FR ES PL...

Page 2: ...3 1 M a x 6 5 0 m 35 300 1080 225 4 5 0 M a x 6 2 0 m A 460 170 255 310 F F A B C VE P650 OPTIONAL E D 2 3 P A C V...

Page 3: ...4 6 V T M D L 4 5 STANDARD...

Page 4: ...al stop for closing Mech Halt Schlie ung Arr t m canique fermeture Tope mec nico cierre Mechanizm zatrzymuj cy zamykanie D Dado tensionamento molla Spring tensioning nut Federspannmutter crou de mise...

Page 5: ...i na zwalnianie i zamnkni cia O Camma finecorsa apertura Opening limit stop cam Endschalternocken ffnen Came fin de course d ouverture Leva fin de carrera de apertura Krzywka kra c wki otwarcia Fineco...

Page 6: ...zelle vom Empf nger 4 Blinker VE L650 5 Pufferbatterien 2 Stck 12V 6 serienweise angeschlossen 6 Selektor 7 Druckregler SC PP 8 Pneum Anschlag SC P35 9 Grundplatte f r Batterien zusammen mit der Steue...

Page 7: ...RG PRG PRG PRG tca fsts sldo sldc tsmo pmo pmc pso psc seav sear 20 99 50 50 20 tsmc 20 20 20 20 0 0 TLS 60 saso 0 sasc 0 0 AUX1 PRG 2 AUX2 20 LOG RADI TCA tca IBL IBCA SCL PP PRE htr ltca tst1 tstm c...

Page 8: ...Die Taste PG dr cken Appuyez sur la touche PG Presionar la tecla PG Wcisn przycisk PG Premere simultaneamente e Press simultaneously keys and Gleichzeitig und dr cken Presser simultan ment et Presiona...

Page 9: ...ANT CLOSE P P U5 F3 MOT AUX 24V BLINK AUX2 COM SWO SWC STOP PHOT OPEN SHLD ANT CLOSE P P MOT AUX ANT M LAMP 24Vdc 24Vdc 500 mA CP LADY BAR LIGHT 24Vdc L LED 1 LED 2 F1 N SA 24V 100 250 Vac 2xDA BT2 Op...

Page 10: ...24Vac 24Vac COM NC NO RX TX 24Vdc COM AUX1 PHOT 24Vdc AUX1 AUX1 0004 tst1 on SCA PHOTOTEST AUX1 0000 AUX1 0003 24Vdc AUX1 SERVICE LIGHT L N 230Vac LAMP 24Vac LAMP Rel 24Vdc MASTER Menu BUS ID 0 SLAVE...

Page 11: ...ompleting installation secure the box to the barrier case again An omnipolar switch section switch with remote contact opening equal to or higher than 3mm must be provided on the power supply mains Ma...

Page 12: ...to that of normal rolling code transmitters with HCS coding but be aware that 1 ARC transmitters and Rolling Code HCS can not be stored in a single receiver 2 The first transmitter memorized determine...

Page 13: ...he unlocking lever is found inside the barrier column Lower the lever to release the shaft Bring the lever back to its original position to reset automatic movement of the shaft 10 MECHANICAL STOPS AD...

Page 14: ...o the function 7 Press the button PG the display shows the signal PRG which indicates that programming has been completed 13 2 PROGRAMMING NOTES Simultaneously pressing and from inside a function menu...

Page 15: ...ean contact 0 Open barrier light close contact when the barrier is open open contact when the barrier is close intermittent during the maneuver fig 11 SCA 1 Second radio cannel of the built in receive...

Page 16: ...ivated only with connected and operating emergency batteries On Activated function In the event of power failure the control unit causes an opening operation The barrier remains open until the power s...

Page 17: ...e typed in by using the numbers from 0 to 9 and the letters A B C D E F The default value is 0000 four zeros and shows the absence of a protection code While typing in the code this operation can be c...

Page 18: ...F3 CP LADY T1A Fuse for the protection of the accessories power supply F1 SA 24V T4A Fuse for general protection 18 BACK UP BATTERIES The control unit CP LADY includes the power pack SA 24V predispose...

Page 19: ...rection until it is blocked Maintenance Every month check the good operation of the emergency manual release It is mandatory not to carry out extraordinary maintenance or repairs as accidents may be c...

Page 20: ...62 7 2 3 4 5 6 1 Ref Code Note 1 9686556 2 968601519 3 96861520 4 9686107 5 9686109 6 7 968601521...

Page 21: ...15 15 I 13 14 11 12 16 16 I 17 18 19 Ref Code Note 9 9686120 10 9686160 11 9686116 12 9686118 13 9686115 14 9686117 15 9686114 15 I 9686318 16 9686113 16 I 9686316 17 9686119 18 9686666 19 968601410...

Page 22: ...AUTOMATISMI BENINC SpA Via Capitello 45 36066 Sandrigo VI Tel 0444 751030 r a Fax 0444 759728...

Reviews: