RediStart MX
2
- SEP Synchronous Controller User Manual
120
30031/40031
Phase Current
—
0: no
line
1: ABC
2: CBA
3: SPH
—
30032/40032
Line Frequency
—
230 – 720, or 0 if no line
0.1 Hz
30033/40033 Analog
Input
%
—
-1000 to +1000 (in 16-bit two's compliment signed
format)
0.1%
30034/40034
Motor Slip %
—
0 – 1000
0.1%
30035/40035
Running Time
—
0 – 65535
hours
30036/40036
Running Time
—
0 – 59
minutes
30037/40037
Number of Starts
—
0 – 65535
30100/40100
Current Setpoint Parameter
R/W
1 – 1000
Arms
30101/40101
Slip Percentage
R/W
5 – 100
0.1%
30102/40102
Field Application Delay Enable
R/W
0:
Disable
1:
Enable
—
30103/40103
Field Application Delay
R/W
1 – 200
0.1 sec
30104/40104
Field Forcing Level
R/W
50 - 125
%
30105/40105
Field Forcing Enable
R/W
0:
Disable
1:
Enable
—
30106/40106
Field Forcing Time
R/W
1 – 900
0.1 sec
30107/40107
Incomplete Sequence Time
R/W
1 – 200
Sec
30108/40108
Pullout Mode
R/W
0:
fault immediately
1:
retry after delay
2:
ride through
—
30109/40109
Pullout Delay Time
R/W
1 – 30
Sec
30110/40110
Resync Retry Attempts
R/W
1 – 10
—
30111/40111
Stop Mode
R/W
0:
Coast
1:
Dyn brake
—
30112/40112
Dynamic Brake Level
R/W
10 – 110
% RFA
30113/40113
Dynamic Brake Time
R/W
1 – 180
Sec
30114/40114
Dynamic Brake Delay
R/W
1 – 50
0.1 Sec
30115/40115
Inching Field Current
R/W
75 - 125
% RFA
30116/40116
Inching Field Application Delay Time
R/W
0 – 900
0.1 Sec
30117/40117
Inching UTS Relay Delay
R/W
1 – 900
0.1 Sec
30118/40118
Meter
R/W
0:
Status
1:
Ave Current
2:
Ave Voltage L-L
3:
L1-L2 Voltage
4:
L2-L3 Voltage
5:
L3-L1 Voltage
6:
Phase Order
7:
Slip %
8:
Line Frequency
9:
Analog Input
10:
Analog Output
11:
Running Days
12:
Running Hours
13:
Starts
—
30119/40119
Open Field Trip Enable
R/W
0:
Disable
1:
Enable
—
30120/40120
Open Field Trip Time
R/W
1 – 900
Sec
30121/40121
Overcurrent Trip Enable
R/W
0:
Disable
1:
Enable
—
Absolute Register
Address
Description
R/W
Range
Units
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...