2.3
Environmental Conditions
2.4
Altitude
Derating
Benshaw controllers are capable of operating at altitudes up to 3,300 feet (1000 meters) without requiring
altitude derating. Table 6 provides the derating percentage to be considered when using a controller above
3,300 feet (1000 meters).
For derating above 10,000 feet consult Benshaw Inc.
2.5
Approvals
The MX
2
SEP Control Card is UL, cUL Recognized
2.6
Certificate of Compliance
CE Mark, see Appendix D on Page 117.
Table 3: Environmental Ratings
Operating Temperatures
–10°C to +40°C (14°F to 104°F) enclosed
–10°C to +50°C (14°F to 122°F) open
Storage Temperatures
–20°C to +70°C (–4°F to 155°F)
Humidity
0% to 95% non condensing
Altitude
1000m (3300ft) without derating
Maximum Vibration
5.9m/s
2
(19.2ft/s
2
) [0.6G]
Cooling
Natural convection (Fans optional)
Table 4: Altitude Derating
Altitude
Percent Derating
(Amps)
3300 Feet
1006 meters
0.0%
4300 Feet
1311 meters
3.0%
5300 Feet
1615 meters
6.0%
6300 Feet
1920 meters
9.0%
7300 Feet
2225 meters
12.0%
8300 Feet
2530 meters
15.0%
9300 Feet
2835 meters
18.0%
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...