RediStart MX
2
- SEP Synchronous Controller User Manual
64
CFN 03 / P4
Field Force Level
LCD / LED
Displays
CFN: F Force Lvl
03 120%
Range
50 – 125% (Default: 120)
Description
The Field Force Level allows a user to over drive the field at synchronization for a programmed time. This is
most commonly used where the load takes more time to stabilize or the application requires a higher magnitude
of torque to synchronize.
NOTE
: May require a higher voltage field supply transformer to produce the desired current.
NOTE
: Not used in Current control mode.
CFN 04 / P5
Field Force Time
LCD / LED
Displays
CFN: F Force Time
04 0.1
Range
Off, 0.1 – 90.0 (Default: 0.1)
Description
The Field Force Time sets how long the system will apply the field forcing current before dropping to the
programmed current.
NOTE:
Not used in Current Control mode (FUN 09 / P39).
CFN 05 / P10
Stop Mode
LCD / LED
Displays
CFN: Stop Mode
05 Coast
Range
Coast, Dyn Brake (Default: Coast)
Description
One of two Stop Modes can be chosen.
Coast:
When Coast mode is selected the controller will immediately remove the DC field when a stop command is
received. The controller will perform a sequenced stop to ensure the motor field is properly removed.
Dynamic Braking:
When Dynamic brake mode is selected the controller will perform a dynamic braking sequence. The controller
will maintain the motor field current and sequence a braking resistor to quickly stop the motor.
NOTE:
The motor controller must have a contactor and dynamic braking resistor installed to use dynamic
braking.
NOTE:
Brush type motor only. (FUN 09 / P39) set to “Field Type”.
120
0
.1
CoS
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...