2.6 Electrical Installation
All electrical wiring and connections must be
in accordance with the relevant European,
National, and Local regulations as well as to
IEE Standards.
Warning
Ensure that the Electric and gas supplies are
turned off before any electrical work is
carried out on the heater. Also ensure that
wiring cannot make contact with any metal
surfaces liable to be subject to high
temperatures, and where insulation of the
wiring could be impaired as a result of such
contact.
All GUH models must be earthed.
Caution
The main electrical supply must not be
switched off or disconnected as a method for
stopping the heater, the exception to this is in
the event of an emergency, or when the
heater has been allowed to cool sufficiently
to prevent any damage from being sustained
to the heater or its controls (ie: during
servicing).
Claims for damage will not be considered if
they have resulted from incorrect wiring or
the incorrect use of the heater
Each heater requires a permanent 230V
50Hz 1ph electrical supply, which must be
wired through a fused isolator fitted with a
fuse of the correct rating (see section 7.1).
The correct supply connection points for the
live, neutral, and earth are clearly indicated
on the wiring diagram mounted inside the
wiring box cover.
Wiring diagrams are also detailed within this
manual, (section 6.0 )
The electrical supply isolator should be
mounted adjacent to the air heater in an
easily accessible position to allow for
servicing isolation, or emergency shut off.
2.7 Electrical panel
Warning
Ensure that the mains isolator is turned OFF
before undertaking any electrical on the
heater.
Access to the electrical panel is gained by
removing the right hand heater side panel,
(Lift the panel clear of the lower lip, pull panel
outwards and let it slide until it is retained by
the two lugs and the lower lip.
The panel can be fully removed by tilting one
of the top corners towards the heater thereby
disengaging the lugs).
The cover to the electrical panel can be
removed by undoing the two screws which
secure it to the panel.
Warning
Ensure that all connections are secure and
that there are no loose strands which could
bridge across the terminals.
A minimum conductor size of 1.0 mm
(diameter) is required.
Caution
One electrical
panel per heater
is required,
unless heaters
are specified for
multiple heater
control
applications. On
no account
should more
than one heater
be connected to
a single time
switch or
thermostat. The
Summary of Contents for GUHA
Page 6: ......
Page 26: ...GUH 50 to 165 Piezo Ignition 6 0 Wiring Diagrams GUH 205 325 Piezo Ignition...
Page 27: ...GUH 400 408 Piezo Ignition GUH 50 325 Automatic Ignition...
Page 28: ...GUH 400 480 Automatic Ignition T CP 2 Control GUH 50 325 Piezo ignition...
Page 29: ...CP 2 Control GUH 50 325 Auto reset CP 2 Control GUH 400 480 Auto reset...
Page 30: ...CP4 Control GUH 400 480 CP 4 Control GUH 50 325...