If for any reason the pilot light is
extinguished
no attempt should be made
to re light it within three minutes
a) Switch on electrical supply
b) Turn on gas supply, and open burner
viewing port
c) Depress and hold in control start button
whilst operating igniter until pilot light is
present
dl) Hold in start button for at least one minute
to establish pilot - carefully release button
confirming presence of pilot
Warning
If the pilot fails to become established
do not
attempt to re light for at least three minutes ,
if the pilot is established continue as follows.
e) Close burner viewing port
f) Set the thermostat to the highest setting,
and the main burner will light then re-open
the viewing port and check that the main
burner is providing a good flame i.e. even,
stable, and conical.
Caution
If the fan fails to operate within approximately
two minutes and the heater goes to overheat
it will shut down through breaking the circuit
to the gas valve, the cause must be
ascertained and rectified before re-ignition.
Once the limit thermostat has tripped out it
must be manually reset to allow re-ignition to
take place.
g) Set controls as required
10.4 Ignition sequence automatic
versions
Automatic control is by way of a Satronic
controller (with automatic gas valve replacing
the manual standing pilot valve) used in
conjunction with a Satronic spark generator
(which replaces the piezo igniter as fitted to
manual units) , giving a maximum pilot
sequence of 15 seconds.
Flame supervision is via a flame sensor rod.
instead of the thermocouple as fitted to the
manual units.
The sequence is as follows: as per 10.3 a-i
The start signal will ignite the pilot, once the
flame proving has taken place the main gas
valve will supply the burner and burner
ignition will occur.
10.5 Stop procedure
(a) Set controller to off position.
(b) The fan motor will continue to run until
heat dissipation allows the fan and limit stat
to shut down the fan.
Caution
Do not use the main electrical isolator to turn
off the heater, to do so can cause damage to
the heat exchanger and combustion
chamber, and thereby invalidate the
warranty.
10.6 Shut down procedure
(
a) Follow steps 10.5 (a) and (b), when fan
stops turn main electrical isolator off, and
shut gas supply cock
10.7 Ventilation only
(
a) Set heat/ventilate switch to 'ventilate'.
10.8 Lockout situations
If either the burner or the fan and limit stat go
to lockout, the lockout must be cleared
manually before the ignition sequence can
be re-initiated.
Caution
Repeated or frequent lockouts must be
investigated and their cause determined by a
qualified and competent engineer.
Summary of Contents for GUHA
Page 6: ......
Page 26: ...GUH 50 to 165 Piezo Ignition 6 0 Wiring Diagrams GUH 205 325 Piezo Ignition...
Page 27: ...GUH 400 408 Piezo Ignition GUH 50 325 Automatic Ignition...
Page 28: ...GUH 400 480 Automatic Ignition T CP 2 Control GUH 50 325 Piezo ignition...
Page 29: ...CP 2 Control GUH 50 325 Auto reset CP 2 Control GUH 400 480 Auto reset...
Page 30: ...CP4 Control GUH 400 480 CP 4 Control GUH 50 325...