1701ULTRA(EC)GBEN, p. 22/29 

 

12.

 

MAINTENANCE

 

Attention

 

 

It

 

is

 

recommended

 

that

 

maintenance

 

is

 

carried

 

out

 

at

 

least

 

once

 

a

 

year.

 

More

 

frequent

 

servicing

 

may

 

be

 

required

 

dependent

 

upon

 

the

 

environmental

 

circumstances

 

where

 

the

 

air

 

heater

 

is

 

installed.

 

Regular

 

inspection

 

is

 

necessary,

 

especially

 

in

 

dirty

 

areas,

 

to

 

assess

 

the

 

servicing

 

frequency.

 

 

Removal

 

of

 

service

 

panel

 

1.

 

Remove

 

door

 

lock

 

at

 

upper

 

and

 

underside.

   

2.

 

Lift

 

the

 

panel

 

holding

 

it

 

at

 

the

 

bottom.

  

 

Substitution

 

of

 

combustion

 

air

 

fan

 

1.

 

Turn

 

off

 

the

 

main

 

gas

 

supply.

  

2.

 

Set

 

the

 

room

 

thermostat

 

so

 

there

 

is

 

no

 

heat

 

demand.

       

3.

 

Wait

 

until

 

the

 

air

 

circulation

 

fan

 

has

 

stopped

 

running.

 

4.

 

Check

 

that

 

the

 

electrical

 

supply

 

is

 

turned

 

off.

  

5.

 

Remove

 

the

 

service

 

panel

 

(see

 

‘removal

 

of

 

service

 

panel’).

 

6.

 

Disconnect

 

the

 

plugs

 

from

 

the

 

combustion

 

air

 

fan.

  

7.

 

Remove

 

the

 

bolts

 

between

 

the

 

combustion

 

air

 

fan

 

and

 

the

 

(bent)

 

gas

 

supply

 

tube.

 

Remove

 

the

 

gasket.

  

8.

 

Remove

 

the

 

fixing

 

screws

 

(or

 

the

 

assembly

 

in

 

case

 

of

 

a

 

ULTRA

 

075/100

 

EC)

 

connecting

 

the

 

air

 

intake

 

restriction

 

and

 

the

 

combustion

 

air

 

fan.

 

9.

 

The

 

combustion

 

air

 

fan

 

can

 

now

 

be

 

removed.

 

10.

 

Remove

 

all

 

the

 

dust

 

from

 

the

 

combustion

 

air

 

fan

 

with

 

a

 

soft

 

cloth

 

or

 

brush.

  

11.

 

Check

 

that

 

the

 

motor

 

and

 

the

 

turbine

 

are

 

undamaged.

  

12.

 

Replace

 

all

 

parts

 

in

 

reverse

 

order.

  

 

Substitution

 

of

 

bulb

 

thermostat

 

LC3

 

1.

 

Wait

 

until

 

the

 

air

 

circulation

 

fan

 

has

 

stopped

 

running.

  

2.

 

Before

 

starting,

 

ensure

 

that

 

the

 

electrical

 

supply

 

is

 

turned

 

off

 

and

 

locked.

  

3.

 

Remove

 

the

 

service

 

panel

 

(see

 

‘removal

 

of

 

service

 

panel’).

 

4.

 

Remove

 

the

 

bracket

 

by

 

using

 

the

 

LC3.

 

5.

 

Disconnect

 

the

 

electrical

 

connections

 

on

 

the

 

bulb

 

thermostat.

 

6.

 

Remove

 

the

 

fixing

 

screws

 

connecting

 

the

 

bulb

 

thermostat

 

to

 

the

 

electrical

 

wiring

 

panel.

 

7.

 

The

 

whole

 

bulb

 

thermostat

 

is

 

now

 

loose

 

and

 

can

 

be

 

removed.

 

8.

 

Replace

 

all

 

parts

 

in

 

reverse

 

order.

 

 

Substitution

 

of

 

bulb

 

thermostat

 

LC1

 

1.

 

Remove

 

the

 

thermocouple

 

via

 

the

 

air

 

outlet

 

side

 

of

 

the

 

air

 

heater.

 

2.

 

Follow

 

the

 

above

 

instructions

 

No

 

6

 

to

 

8

 

for

 

the

 

bulb

 

thermostat

 

LC3.

 

 

Cleaning

 

&

 

substitution

 

of

 

burner

 

When

 

cleaning

 

and

 

re

installing

 

the

 

burner,

 

it

 

is

 

necessary

 

to

 

make

 

use

 

of

 

a

 

kit

 

specially

 

designed

 

for

 

ULTRA/ULTRA

 

EC

 

units.

  

Use

 

only

 

kits

 

which

 

are

 

approved

 

by

 

the

 

manufacturer

 

and

 

which

 

are

 

appropriate

 

for

 

your

 

appliance.

 

Use

 

kit

 

number

 

36

 

25192

 

025

 

for

 

unit

 

ULTRA

 

(EC)

 

type

 

025

 

 

For

 

all

 

other

 

types,

 

use

 

kit

 

number

 

36

 

25192

 

035.

   

Always

 

consult

 

your

 

distributor

 

at

 

the

 

slightest

 

doubt.

 

 

 

 

 

 

 

 

Summary of Contents for ULTRA 025(EC)

Page 1: ...EC This appliance meets the following EC Directives DIR 2009 142 EC GAD DIR 2014 30 EU EMC DIR 2014 35 EU LVD DIR 2006 42 EC MD INSTALLATION COMMISSIONING SERVICING USER INSTRUCTIONS ATTENTION The man...

Page 2: ...connection Gas supply 17 10 Electrical connections 19 11 Commissioning lighting operation 21 12 Maintenance 23 13 Fault finding 25 14 Spare parts list 27 15 User instructions 27 16 Declaration of conf...

Page 3: ...owledge unless they have been given supervision or instructions concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play w...

Page 4: ...etc The installation is not in accordance with these instructions Wiring is not in accordance with the diagram furnished with the heater Unit is installed without proper clearance to combustible mater...

Page 5: ...harge air along exposed walls with extra units provided to discharge air towards the centre of the area For optimum results heaters are best used in conjunction with recirculating air fans suspended a...

Page 6: ...Protection grade IP Revolutions per minute main fan rpm 950 1260 1340 820 1400 CE Approval number PIN 1 2 G 3 4 G I2H or I3P B22p C12 C32 C42 C52 C62 C82 Max thermal efficiency at max heat input G20...

Page 7: ...ctrical connections 2 Flue connection D 5 Service panel 3 External gas connection C 6 Condensate drain ULTRA ULTRA EC A B C D E F I J K L M 025 738 1217 1 2 G 80 82 405 55 449 135 311 120 035 738 1217...

Page 8: ...p 8 29 Figure 1b ULTRA ULTRA EC 100 all dimensions in mm tolerance 3mm 1 Combustion air inlet 100mm 4 Electrical connections 2 Flue connection 100mm 5 Service panel 3 External gas connection 3 4 G 6...

Page 9: ...100 100 100 820 100 500 100 100 100 820 Heaters can be mounted on suitable non combustible supports 5 INTERNAL LAYOUT Figure 3 1 Metal mesh burner 2 Zero pressure regulator 3 Venturi 4 Differential p...

Page 10: ...t suspension All points must be used Threaded nut inserts are provided on each side of the top of the heater See figure 4 After suspension the air heater should be rigid so as to avoid placing a strai...

Page 11: ...n cause unsafe conditions and or create condensation The units may be installed as a balanced flue type C heater requiring both a combustion air inlet pipe and a flue pipe or as a power vented heater...

Page 12: ...all other relevant regulations rules in force Single wall flue pipe seamless aluminium stainless steel pipes are required All joints must be sealed to prevent products of combustion from leaking into...

Page 13: ...1701ULTRA EC GBEN p 13 29 Figure 7 Type C appliances combustion air and flue pipe sockets VERTICAL FLUE KIT OPTION 302 HORIZONTAL FLUE KIT OPTION 301...

Page 14: ...lation improved vapour barriers and weather proofing These practices mean that buildings are sealed much tighter than in the past Model ULTRA ULTRA EC 025 035 050 075 100 Max straight concentric lengt...

Page 15: ...nt condensation water dripping from the drain pipe If you want to open the siphon e g to clean it the air heater must be shut down For security reasons it is recommended to wear gloves when cleaning t...

Page 16: ...ater a gas tap with coupling must be mounted for servicing see figure 11 It is strongly recommended to place a gas filter and clean the gas tube with nitrogen The whole of the gas service installation...

Page 17: ...the venturi Throttle adjustments and CO2 measurements will have to be made in order to obtain the recommended CO2 value For details please see the CO2 Throttle adjustment section 9 3 Attention Always...

Page 18: ...n make connections to the terminals in the electric box as indicated on the wiring diagram Ensure that all cables and installers wiring are appropriately fixed and that they do not touch the flue comb...

Page 19: ...idual on off control 0 or 100 functioning 2 By means of option 952 weekly programming digital chronothermostat GA11 used for remote control of several units consult option 952 instruction for more det...

Page 20: ...shed during a run cycle an automatic attempt for re ignition will take place If the burner does not relight safety shut down and lockout will occur Manual intervention to reset will be necessary to pu...

Page 21: ...uring which the combustion fan operates prior to activation of the ignition device The safety time is the delay between the gas valve being energised and the flame sensor checking for the presence of...

Page 22: ...ve all the dust from the combustion air fan with a soft cloth or brush 11 Check that the motor and the turbine are undamaged 12 Replace all parts in reverse order Substitution of bulb thermostat LC3 1...

Page 23: ...nel see removal of the service panel 4 Disconnect the electrical connections of the air circulation fan These connections are on the electrical connections terminal see the wiring diagram 5 Loosen the...

Page 24: ...the unit is grounded earthed YES Connect ground wire to unit chassis Replace flame sensor Replace control module YES YES In case of a LL net swap the 2 lines NO Check if the igniter sparks Check prese...

Page 25: ...rameters YES Replace Pressure switch NO Check copper pipe inside the unit is not clogged Replace copper tube Check if the cooling fan works within set parameters NO Replace cooling fan NO Check if the...

Page 26: ...RZ29 035 100 reset switch 60 61988 2645 all signal lamp 60 61997 all pressostat 30 60621 13 605 all venturi gas valve 03 25700 003 0 0 3 025 venturi gas valve 40cm tube 03 25700 051 0 51 035 venturi g...

Page 27: ...set by pushing reset button inside the appliance or the remote control b check if thermal overheat control requires resetting 7 If the thermal overheat control requires resetting and doing so restarts...

Page 28: ...1701ULTRA EC GBEN p 28 29 16 DECLARATION OF CONFORMITY...

Page 29: ...mbiradsales nortek com www ambirad co uk Registered in England N 1390934 Registered office 10 Norwich Street London EC4A 18D Nortek Global HVAC is a registered trademark of Nortek Global HVAC Limited...