background image

1704VRC3-AMEN, p 16/35 

               

GENERAL

 

REQUIREMENTS

 

 

3.1

 

Related

 

documents

 

 

It

 

is

 

important

 

that

 

all

 

gas

 

appliances

 

are

 

installed

 

in

 

accordance

 

with

 

the

 

rules

 

in

 

force

 

and

 

by

 

appropriately

 

qualified

 

persons.

 

Failure

 

to

 

install

 

appliances

 

correctly

 

could

 

lead

 

to

 

prosecution.

 

It

 

is

 

in

 

your

 

own

 

interest

 

and

 

that

 

of

 

safety

 

to

 

ensure

 

compliance

 

with

 

the

 

law.

 

 

Air

 

heaters

 

should

 

not

 

be

 

installed

 

in

 

corrosive

 

atmospheres,

 

i.e.

 

near

 

plating

 

or

 

degreasing

 

plants

 

or

 

in

 

areas

 

where

 

there

 

is

 

a

 

fire

 

risk.

 

Do

 

not

 

locate

 

the

 

air

 

heater

 

where

 

it

 

may

 

be

 

exposed

 

to

 

water

 

spray,

 

rain,

 

etc.

 

 

3.2

 

Heater

 

location

 

 

The

 

location

 

chosen

 

for

 

the

 

air

 

heater

 

must

 

permit

 

the

 

provision

 

of

 

a

 

satisfactory

 

flue

 

system

 

venting

 

to

 

outdoor

 

atmosphere

 

and

 

adequately

 

ventilated

 

to

 

provide

 

for

 

combustion

 

air.

 

The

 

location

 

must

 

also

 

provide

 

sufficient

 

space

 

to

 

allow

 

the

 

heater

 

to

 

be

 

serviced.

 

 

Table

 

3

 

Minimum

 

installation

 

clearances

 

(mm)

Table

 

4 Recommended mounting

 

heights

  

(m)

 

(*)

 

 
 
 
 
 
 
 

*

 

Measure

 

rear

 

clearance

 

from

 

the

 

back

  

of

 

the

 

motor

 

 

 
 
 

*

 

Height

 

from

 

floor

 

to

 

bottom

 

surface

 

of

 

heater.

   

These

 

are

 

recommendations

 

only.

   

Positioning

 

of

 

heaters

 

depends

 

on

 

application.

 

 

Air

 

heaters

 

should,

 

where

 

ever

 

possible

 

always

 

be

 

installed

 

to

 

blow

 

toward

 

or

 

along

 

external

 

wall

 

surfaces.

 

Where

 

two

 

or

 

more

 

air

 

heaters

 

are

 

installed

 

in

 

the

 

same

 

room,

 

a

 

general

 

scheme

 

to

 

ensure

 

continuous

 

air

 

circulation

 

should

 

be

 

maintained

 

for

 

best

 

results.

 

Suspended

 

heaters

 

are

 

most

 

effective

 

when

 

located

 

as

 

close

 

to

 

the

 

occupancy

 

zone

 

as

 

possible,

 

this

 

fact

 

should

 

be

 

born

 

in

 

mind

 

when

 

determining

 

the

 

mounting

 

heights

 

to

 

be

 

used.

 

Care

 

should

 

be

 

exercised

 

to

 

avoid

 

directing

 

warm

 

air

 

directly

 

onto

 

the

 

occupants.

 

Partitions,

 

columns,

 

counters,

 

storage

 

racking,

 

etc.

 

should

 

be

 

taken

 

into

 

account

 

when

 

choosing

 

the

 

location

 

so

 

that

 

an

 

unobstructed

 

path

 

for

 

the

 

air

 

circulation

 

can

 

be

 

maintained.

 

Where

 

air

 

heaters

 

are

 

located

 

in

 

the

 

centre

 

of

 

the

 

space

 

to

 

be

 

heated,

 

the

 

air

 

should

 

be

 

discharged

 

toward

 

outside

 

walls.

 

In

 

large

 

areas,

 

they

 

should

 

be

 

located

 

to

 

discharge

 

air

 

along

 

outside

 

walls

 

with

 

additional

 

heaters

 

provided

 

to

 

blow

 

air

 

into

 

the

 

centre

 

of

 

the

 

area.

 

In

 

places

 

where

 

infiltration

 

of

 

cold

 

is

 

excessive,

 

such

 

as

 

entrance

 

doors

 

it

 

is

 

desirable

 

to

 

locate

 

a

 

heater

 

so

 

that

 

warm

 

air

 

is

 

discharged

 

directly

 

toward

 

the

 

source

 

of

 

cold

 

air

 

from

 

a

 

distance

 

of

 

4,5

 ‐ 

6,0

 

metres.

 

 

3.3

 

Combustion

 

air

 

supply

 

&

 

flue

 

system

 

 

The

 

air

 

heater

 

may

 

be

 

installed

 

as

 

a

 

balanced

 

flue

 

(Type

 

C)

 

heater

 

requiring

 

both

 

a

 

combustion

 

air

 

inlet

 

duct

 

and

 

a

 

flue

 

pipe

 

or

 

as

 

a

 

power

 

vented

 

(Type

 

B)

 

heater,

 

which

 

requires

 

only

 

a

 

flue

 

pipe

 

exhausting

 

to

 

outdoors.

 

All

 

products

 

of

 

combustion

 

must

 

be

 

flued

 

to

 

outdoor

 

atmosphere.

  

Each

 

heater

 

installed

 

as

 

a

 

type

 

B

 

appliance

 

must

 

be

 

fitted

 

with

 

an

 

individual

 

flue

 

pipe

 

and

 

the

 

combustion

 

air

 

inlet

 

opening

 

must

 

be

 

provided

 

with

 

a

 

protection

 

grill

 

(ask

 

your

 

distributor

 

for

 

the

 

appropriate

 

protection

 

grill

   

(IP20)

 

(dia130

 

=

 

PN

 

02

 

25094

 

).

 

Each

 

heater

 

installed

 

as

 

a

 

type

 

C

 

appliance

 

must

 

be

 

fitted

 

with

 

an

 

individual

 

combustion

 

air/flue

 

pipe

 

system.

 

Only

 

systems

 

specified

 

by

 

the

 

air

 

heater

 

manufacturer

 

may

 

be

 

used.

 

Common

 

flue

 

and

 

combustion

 

air

 

systems

 

must

 

not

 

be

 

used!

 

Figure

 

2a

 

:

 

Combustion

 

air

 

and

 

flue

 

pipe

 

sockets

 

1

 

Flue

 

outlet

 

socket

 

2

 

Combustion

 

air

 

inlet

 

opening

  

3

 

Gas

 

connection

 

inlet

 

with

 

sealing

 

ring

 

4

 

Electrical

 

connections

 

 

VRC-3

20

30

45

others

Mounting height

3

4

5

VRC-3

100

Top

150

Flue connector

150

Access panel

500

Non access sid

150

Bottom

150

Rear*

250

Summary of Contents for VRC-3 100-3

Page 1: ...perty damage injury or death All work must be carried out by appropriately qualified persons The manufacturer does not take any responsibility in the event of non observance of the regulations concerning the connection of the apparatus causing a dangerous operation of the apparatus possibly resulting in damage to the apparatus and or environment in which the unit is installed Please read this docu...

Page 2: ...urner Injectors 8 3 Ignition System 8 4 Operating Gas Valve 8 5 Limit Controls 8 6 Combustion Air Pressure Switch 8 7 Combustion Air Fan 9 0 FAULT FINDING 10 0 PARTS LIST 11 0 GAS CONVERSION 12 0 USERS INSTRUCTIONS 13 0 HEALTH SAFETY STATEMENT HAZARD INTENSITY LEVELS DANGER Failure to comply will result in severe personal injury or death and or property damage WARNING Failure to comply could resul...

Page 3: ...NICAL DATA 2 1 Specifications Table 1 20 30 45 60 75 100 Gas category Comb Air Flue Type B 1 Comb Air Flue Type C 1 Connection colars mm 100 100 130 130 130 130 Heat inputs Hs kW 26 42 31 63 54 38 73 25 87 85 114 87 Heat inputs Hi kW 23 80 28 50 49 00 66 00 79 15 103 50 Heat output kW 21 82 25 99 44 64 60 92 73 13 94 50 Thermal efficiency 91 70 91 20 91 10 92 30 92 39 91 30 Gas consumption G20 m3 ...

Page 4: ...0 12 mm 1 15 1 15 1 15 1 45 1 45 1 50 marking 115 115 115 145 145 150 Butane 28 10 28 10 28 14 27 90 27 75 26 96 Propane 35 80 35 80 35 90 35 60 35 40 34 40 Injector size Burner pressure mbar 1 2 2 Burner pressure injector size Table 2A Injector size and burner pressure G20 natural gas Inlet pressure 20 0 mbar Table 2B Injector size and burner pressure G30 G31 butane propane Inlet pressures G30 28...

Page 5: ...1704VRC3 AMEN p 5 35 VRC 30 3 VRC 45 3 ...

Page 6: ...1704VRC3 AMEN p 6 35 VRC 60 3 VRC 75 3 ...

Page 7: ...1704VRC3 AMEN p 7 35 2 4 Blower options 2 4 1 Mixing cabinet Bottom exit Rear exit closed open open closed half half Damper position VRC 100 3 VRC 20 3 with mix box ...

Page 8: ...1704VRC3 AMEN p 8 35 VRC 30 3 with mix box VRC 45 3 with mix box ...

Page 9: ...1704VRC3 AMEN p 9 35 VRC 60 3 with mix box VRC 75 3 with mix box ...

Page 10: ...1704VRC3 AMEN p 10 35 2 4 2 Mixing cabinet and filters VRC 100 3 with mix box VRC 20 3 with mix box and filters ...

Page 11: ...1704VRC3 AMEN p 11 35 VRC 30 3 with mix box and filters VRC 45 3 with mix box and filters ...

Page 12: ...1704VRC3 AMEN p 12 35 VRC 60 3 with mix box and filters VRC 75 3 with mix box and filters ...

Page 13: ...4 3 Free blowing Free blowing Dimensions mm LCSC Restriction part no A B C 20 30 1002436 58 70 240 45 1002437 154 154 320 60 1002438 130 154 320 75 1002439 130 154 396 100 1002440 166 178 396 VRC 100 3 with mix box and filters ...

Page 14: ...1704VRC3 AMEN p 14 35 2 5 Dimensions STANDARD UNIT ...

Page 15: ...1704VRC3 AMEN p 15 35 UNIT WITH MIXING CABINET option 526 ...

Page 16: ...r directly onto the occupants Partitions columns counters storage racking etc should be taken into account when choosing the location so that an unobstructed path for the air circulation can be maintained Where air heaters are located in the centre of the space to be heated the air should be discharged toward outside walls In large areas they should be located to discharge air along outside walls ...

Page 17: ...ain or gully The condensation drain from the flue must be constructed from non corrodible material not less than 20 mm diameter Copper or copper based alloys must not be used for condensation drains 3 3 2 Combustion air inlet pipe flue pipe for balanced flue installation Type C appliances Balanced flue air heaters are designed to be fitted with a combustion air inlet pipe that obtains outdoor air ...

Page 18: ...Flue pipe outlet collar 2 combustion air inlet opening 3 5 Air distribution Follow recommended practice for building air distribution The following notes are of particular importance Where free blowing air heaters are installed it must be taken into account that heated air is buoyant when it leaves the appliance therefore air patterns within the space being heated will modify the air throw pattern...

Page 19: ...the installation requirements and the appliance before commencing installation 4 2 Suspending the air heater Before installing the appliance check to ensure that the supporting structure is adequate to carry the weight of the appliance and its ancillaries i e flue system Please check weights specified in table 1 When the heater is lifted for suspension support the bottom of the heater with plywood...

Page 20: ...et socket size dia mm Figure 4 Figure 5 4 4 Gas connection Do not use the appliance gas supply to balance or support any part of the appliance Figure 6 Connection to a gas network may only be carried out by appropriately qualified persons The gas installation must comply with the rules in force using materials appropriate for gas installation To facilitate servicing the air heater must be fitted w...

Page 21: ...side wall Avoid location in draughty areas or where it may be influenced by heat sources e g the sun process plant etc The thermostat or temperature sensor should be mounted on a vibration free surface and mounted about 1 5 metres above floor level Follow the thermostat manufacturers fitting instructions The thermostat must be suitable for switching 230 volts AIR DISTRIBUTION VRC 3 air heaters are...

Page 22: ...riod has elapsed the integral ignitor and multi functional gas control operate The ignition spark ignites the gas creating the burner flame which is detected by a flame rod sensor If a burner flame is not detected the ignition controller proceeds to lock out and requires manually resetting Lock out is indicated by the red warning light on the air heater If the first reset is not successful wait 15...

Page 23: ... control valve Connect a manometer to the test point see figure 7 Adjust the room thermostat to call for heat e g above room ambient temperature Observe the burner gas pressure on the manometer and compare to the required pressure If necessary adjust the burner gas pressure only for natural gas Remove the cover screw Turn the regulator screw anti clockwise to decrease pressure or clockwise to incr...

Page 24: ...ter Ensure they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface Advise the person who is resuming responsibility that for continued safe operation the air heater should be serviced at least once a year SERVICING INSTRUCTIONS IMPORTANT Only appropriately qualified persons may carry out servicing and fault finding on this gas fired e...

Page 25: ...to remove all external dirt Check the security of the fan on the motor Note Fan motors are lubricated for life and do not require lubricating 4 Remove any dirt and or grease that may have accumulated on the venter fan motor and its housing Note The combustion air fan motors are lubricated for life and do not require oiling or greasing 5 The gas multi functional control valve requires no field main...

Page 26: ...operating instructions a copy of which is supplied with the air heater Fig 10b Fitting the ignitor 8 4 Multi functional gas control valve 1 Ensure gas supply to the air heater is turned OFF 2 After the air circulation fan has stopped switch OFF the electricity supply to the air heater 3 Mark for future identification and disconnect the wires connected to the valve 4 Disconnect the gas service unio...

Page 27: ...ricity supply to the air heater 3 To gain access to the fan open the hinged controls compartment access door refer to figure 9 for location 4 Mark for future identification and disconnect the wires connecting the fan motor at the terminals on the main wiring junction 5 Remove combustion air fan and clean as necessary using a wire brush and solvent to remove sticky residues 6 Re assemble and check ...

Page 28: ... dirty Determinewhat causedthe limit totrip Placeintonormal operation Check themains Check thetime tempeature control Is therecontinuitybetween 9 10 Is there230Vbetween 11 12 Is power ventingoperating Reset limit control Check venter motor Replacepressureswitch Isthethermostat above roomtemperatureandif usedisthetime clock ON Set thermostat aboveroom temperature if usedmake certainthetimeclock is ...

Page 29: ... pressure During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visible Check flame signal Is it greater than 1 0 micro Amps Check flame signal using micro amp meter Is signal greater than 1 0 micro Amps During 5 trial for ignition is a flame visible in ths view port Correct polarity Does the inlet gas pre...

Page 30: ...r distribution device been placed on the heater Is there excessive static pressure in the ductwork Did the motor overload trip Does the fan control energize the fan motor in less than 75 Adjust thermostat temp setting above ambient to energize fan gas solenoid valve Replace the motor Consult fan fault finding Does the limit trip before the fan is energized Place system in normal operation Consult ...

Page 31: ...RC 45 3 01 27202 ERP blower VRC 60 3 01 27203 ERP blower VRC 75 3 01 27204 ERP blower VRC 100 3 01 27205 Settings PARTS LISTING GAS CONVERSION VRC 3 air heaters are designed to operate on natural or propane gas and will be supplied fitted for the gas type ordered In the event of site conversion to a different gas type it is necessary to convert the gas burner and burner controls Affix new data pla...

Page 32: ...room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of the appliance and on a remote control if fitted Reset by pushing reset button inside the appliance or the remote control b check if thermal overheat control requires resetting 7 If the thermal overheat control...

Page 33: ...ing and itching of the skin Fiber entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling People with a history of skin complaints may be susceptible to irritation Dust levels are only likely when the material is abraded In general normal handling and use for this purpose will not present disc...

Page 34: ...irective Complies with the requirements of further directives namely GAD 2009 142 EC EMC 2004 108 EC LVD 2006 95 EC the following harmonized standards have been applied EN 1020 Non domestic gas fired forced convection air heaters for space heating not exceeding a net heat input of 300 kW incorporating a fan to assist transportation of combustion air and or combustion products The following notifie...

Page 35: ...1384 489 250 www ambirad co uk Registered in England N 1390934 Registered office 10 Norwich Street London EC4A 18D Nortek Global HVAC is a registered trademark of the Nortek Global HVAC Limited Because of continuous product innovation Nortek Global HVAC reserves the right to change product specification without due notice ...

Reviews: