IMPORTANT:

 

The

 

flue

 

must

 

be

 

installed

 

in

 

accordance

 

with

 

national

 

and

 

local

 

regulations.

 

Failure

 

to

 

provide

 

proper

 

flueing

 

could

 

result

 

in

 

death,

 

serious

 

injury

 

and/or

 

property

 

damage.

 

The

 

air

 

heater

 

must

 

be

 

installed

 

with

 

a

 

flue

 

to

 

the

 

outside

 

of

 

the

 

building.

 

Safe

 

operation

 

of

 

any

 

power

 

vented

 

gas

 

apparatus

 

requires

 

a

 

properly

 

operating

 

flue

 

system,

 

correct

 

provision

 

for

 

combustion

 

air,

 

and

 

regular

 

maintenance

 

and

 

inspection.

 

 

 
 

3.3.1

 

Flues

 

for

 

power

 

vented

 

installations

 

(Type

 

B

 

appliances)

 

 

If

 

the

 

air

 

heater

 

is

 

to

 

be

 

installed

 

as

 

a

 

type

 

B

 

appliance,

 

air

 

for

 

combustion

 

will

 

be

 

taken

 

from

 

within

 

the

 

space

 

where

 

the

 

heater

 

is

 

installed.

 

Ensure

 

that

 

an

 

adequate

 

air

 

supply

 

for

 

combustion

 

and

 

ventilation

 

is

 

provided

 

within

 

the

 

building

 

in

 

accordance

 

with

 

the

 

regulations

 

&

 

rules

 

in

 

force.

 

 

Table

 

5

 

shows

 

flue

 

pipe

 

sizes

 

and

 

maximum

 

pipe

 

lengths.

 

The

 

minimum

 

flue

 

length

 

is

 

0.5

 

metres.

 

Single

 

wall

 

flue

 

pipes

 

are

 

required.

 

All

 

joints

 

must

 

be

 

sealed

 

to

 

prevent

 

products

 

of

 

combustion

 

from

 

leaking

 

into

 

the

 

building.

 

An

 

approved

 

flue

 

terminal

 

is

 

required.

 

 

If

 

the

 

flue

 

passes

 

through

 

a

 

combustible

 

element

 

of

 

the

 

building

 

it

 

must

 

be

 

enclosed

 

by

 

a

 

sleeve

 

of

 

non

combustible

 

material

 

and

 

separated

 

from

 

the

 

sleeve

 

by

 

at

 

least

 

a

 

25

 

mm

 

air

 

break.

  

 

Table

 

5

 

:

 

Flue

 

pipe

 

diameters

 

&

 

maximum

 

lengths

The

 

temperature

 

of

 

any

 

combustible

 

material

 

near

 

to

 

the

 

flue

 

must

 

not

 

exceed

 

65°C

 

when

 

the

 

heater

 

is

 

in

 

operation.

 

The

 

flue

 

must

 

be

 

at

 

least

 

50

 

mm

 

away

 

from

 

any

 

combustible

 

material.

 

Single

 

wall

 

flue

 

pipe

 

exposed

 

to

 

cold

 

air

 

or

 

run

 

through

 

unheated

 

areas

 

must

 

be

 

insulated.

 

Where

 

condensation

 

is

 

unavoidable,

 

provision

 

must

 

be

 

made

 

for

 

the

 

condensation

 

to

 

flow

 

freely

 

to

 

a

 

point

 

to

 

which

 

it

 

can

 

be

 

released,

 

i.e.

 

a

 

drain

 

or

 

gully.

 

The

 

condensation

 

drain

 

from

 

the

 

flue

 

must

 

be

 

constructed

 

from

 

non

corrodible

 

material

 

not

 

less

 

than

 

20

 

mm

 

diameter.

 

Copper

 

or

 

copper

 

based

 

alloys

 

must

 

not

 

be

 

used

 

for

 

condensation

 

drains.

 

 
 

3.3.2

 

Combustion

 

air

 

inlet

 

pipe

 

&

 

flue

 

pipe

 

for

 

balanced

 

flue

 

installation

 

(Type

 

C

 

appliances)

 

 

Balanced

 

flue

 

air

 

heaters

 

are

 

designed

 

to

 

be

 

fitted

 

with

 

a

 

combustion

 

air

 

inlet

 

pipe

 

that

 

obtains

 

outdoor

 

air

 

and

 

a

 

flue

 

pipe

 

that

 

exhausts

 

flue

 

products

 

to

 

outdoors.

 

 

Air

 

heaters

 

if

 

fitted

 

with

 

a

 

power

 

venter

 

permitting

 

either

 

a

 

vertical

 

or

 

horizontal

 

combustion

 

air

 

inlet/flue

 

pipe

 

system.

 

The

 

heaters

 

must

 

be

 

installed

 

with

 

a

 

concentric

 

vertical

 

or

 

horizontal

 

flue/combustion

 

air

 

inlet.

 

The

 

heaters

 

are

 

only

 

approved

 

for

 

use

 

when

 

installed

 

with

 

the

 

appropriate

 

approved

 

concentric

 

vent

 

terminal.

 

See

 

table

 

6.

 

 

Both

 

the

 

flue

 

and

 

combustion

 

air

 

pipes

 

must

 

be

 

sealed.

 

Use

 

gasket

 

sealed

 

seamless

 

aluminum

 

pipe

 

or

 

equivalent.

 

The

 

flue

 

pipe

 

must

 

include

 

a

 

re

sealable

 

test

 

port

 

to

 

allow

 

good

 

average

 

sampling

 

of

 

the

 

flue

 

gas

 

mixture

 

for

 

testing,

 

the

 

port

 

must

 

be

 

at

 

least

 

450

 

mm

 

away

 

from

 

the

 

air

 

heater

 

flue

 

connection

 

socket.

 

 

Follow

 

any

 

flue

 

pipe

 

manufacturers’

 

installation

 

instructions

 

for

 

making

 

joints,

 

including

 

connections

 

to

 

the

 

air

 

heater,

 

for

 

passing

 

through

 

a

 

building

 

element

 

and

 

for

 

support

 

requirements.

 

If

 

more

 

than

 

one

 

air

 

heater

 

is

 

being

 

installed

 

in

 

the

 

same

 

place

 

each

 

heater

 

must

 

have

 

a

 

separate

 

flue

 

system.

 

Where

 

condensation

 

is

 

unavoidable,

 

provision

 

must

 

be

 

made

 

for

 

the

 

condensation

 

to

 

flow

 

freely

 

to

 

a

 

point

 

to

 

which

 

it

 

can

 

be

 

released,

 

i.e.

 

a

 

drain

 

or

 

gully.

 

The

 

condensation

 

drain

 

from

 

the

 

flue

 

must

 

be

 

constructed

 

from

 

non

corrodible

 

material

 

not

 

less

 

than

 

20

 

mm

 

diameter.

 

Copper

 

or

 

copper

 

based

 

alloys

 

must

 

not

 

be

 

used

 

for

 

condensation

 

drains.

 

VRC-3

other sizes

Heater socket & 

mm

pipe dia

Maximum straight 

m

length

Equivalent length 

m

of 45° elbow

Equivalent length 

m

of 90° elbow

9

0.75

1.5

20 & 30

100

130

Summary of Contents for VRC-3 100-3

Page 1: ...perty damage injury or death All work must be carried out by appropriately qualified persons The manufacturer does not take any responsibility in the event of non observance of the regulations concerning the connection of the apparatus causing a dangerous operation of the apparatus possibly resulting in damage to the apparatus and or environment in which the unit is installed Please read this docu...

Page 2: ...urner Injectors 8 3 Ignition System 8 4 Operating Gas Valve 8 5 Limit Controls 8 6 Combustion Air Pressure Switch 8 7 Combustion Air Fan 9 0 FAULT FINDING 10 0 PARTS LIST 11 0 GAS CONVERSION 12 0 USERS INSTRUCTIONS 13 0 HEALTH SAFETY STATEMENT HAZARD INTENSITY LEVELS DANGER Failure to comply will result in severe personal injury or death and or property damage WARNING Failure to comply could resul...

Page 3: ...NICAL DATA 2 1 Specifications Table 1 20 30 45 60 75 100 Gas category Comb Air Flue Type B 1 Comb Air Flue Type C 1 Connection colars mm 100 100 130 130 130 130 Heat inputs Hs kW 26 42 31 63 54 38 73 25 87 85 114 87 Heat inputs Hi kW 23 80 28 50 49 00 66 00 79 15 103 50 Heat output kW 21 82 25 99 44 64 60 92 73 13 94 50 Thermal efficiency 91 70 91 20 91 10 92 30 92 39 91 30 Gas consumption G20 m3 ...

Page 4: ...0 12 mm 1 15 1 15 1 15 1 45 1 45 1 50 marking 115 115 115 145 145 150 Butane 28 10 28 10 28 14 27 90 27 75 26 96 Propane 35 80 35 80 35 90 35 60 35 40 34 40 Injector size Burner pressure mbar 1 2 2 Burner pressure injector size Table 2A Injector size and burner pressure G20 natural gas Inlet pressure 20 0 mbar Table 2B Injector size and burner pressure G30 G31 butane propane Inlet pressures G30 28...

Page 5: ...1704VRC3 AMEN p 5 35 VRC 30 3 VRC 45 3 ...

Page 6: ...1704VRC3 AMEN p 6 35 VRC 60 3 VRC 75 3 ...

Page 7: ...1704VRC3 AMEN p 7 35 2 4 Blower options 2 4 1 Mixing cabinet Bottom exit Rear exit closed open open closed half half Damper position VRC 100 3 VRC 20 3 with mix box ...

Page 8: ...1704VRC3 AMEN p 8 35 VRC 30 3 with mix box VRC 45 3 with mix box ...

Page 9: ...1704VRC3 AMEN p 9 35 VRC 60 3 with mix box VRC 75 3 with mix box ...

Page 10: ...1704VRC3 AMEN p 10 35 2 4 2 Mixing cabinet and filters VRC 100 3 with mix box VRC 20 3 with mix box and filters ...

Page 11: ...1704VRC3 AMEN p 11 35 VRC 30 3 with mix box and filters VRC 45 3 with mix box and filters ...

Page 12: ...1704VRC3 AMEN p 12 35 VRC 60 3 with mix box and filters VRC 75 3 with mix box and filters ...

Page 13: ...4 3 Free blowing Free blowing Dimensions mm LCSC Restriction part no A B C 20 30 1002436 58 70 240 45 1002437 154 154 320 60 1002438 130 154 320 75 1002439 130 154 396 100 1002440 166 178 396 VRC 100 3 with mix box and filters ...

Page 14: ...1704VRC3 AMEN p 14 35 2 5 Dimensions STANDARD UNIT ...

Page 15: ...1704VRC3 AMEN p 15 35 UNIT WITH MIXING CABINET option 526 ...

Page 16: ...r directly onto the occupants Partitions columns counters storage racking etc should be taken into account when choosing the location so that an unobstructed path for the air circulation can be maintained Where air heaters are located in the centre of the space to be heated the air should be discharged toward outside walls In large areas they should be located to discharge air along outside walls ...

Page 17: ...ain or gully The condensation drain from the flue must be constructed from non corrodible material not less than 20 mm diameter Copper or copper based alloys must not be used for condensation drains 3 3 2 Combustion air inlet pipe flue pipe for balanced flue installation Type C appliances Balanced flue air heaters are designed to be fitted with a combustion air inlet pipe that obtains outdoor air ...

Page 18: ...Flue pipe outlet collar 2 combustion air inlet opening 3 5 Air distribution Follow recommended practice for building air distribution The following notes are of particular importance Where free blowing air heaters are installed it must be taken into account that heated air is buoyant when it leaves the appliance therefore air patterns within the space being heated will modify the air throw pattern...

Page 19: ...the installation requirements and the appliance before commencing installation 4 2 Suspending the air heater Before installing the appliance check to ensure that the supporting structure is adequate to carry the weight of the appliance and its ancillaries i e flue system Please check weights specified in table 1 When the heater is lifted for suspension support the bottom of the heater with plywood...

Page 20: ...et socket size dia mm Figure 4 Figure 5 4 4 Gas connection Do not use the appliance gas supply to balance or support any part of the appliance Figure 6 Connection to a gas network may only be carried out by appropriately qualified persons The gas installation must comply with the rules in force using materials appropriate for gas installation To facilitate servicing the air heater must be fitted w...

Page 21: ...side wall Avoid location in draughty areas or where it may be influenced by heat sources e g the sun process plant etc The thermostat or temperature sensor should be mounted on a vibration free surface and mounted about 1 5 metres above floor level Follow the thermostat manufacturers fitting instructions The thermostat must be suitable for switching 230 volts AIR DISTRIBUTION VRC 3 air heaters are...

Page 22: ...riod has elapsed the integral ignitor and multi functional gas control operate The ignition spark ignites the gas creating the burner flame which is detected by a flame rod sensor If a burner flame is not detected the ignition controller proceeds to lock out and requires manually resetting Lock out is indicated by the red warning light on the air heater If the first reset is not successful wait 15...

Page 23: ... control valve Connect a manometer to the test point see figure 7 Adjust the room thermostat to call for heat e g above room ambient temperature Observe the burner gas pressure on the manometer and compare to the required pressure If necessary adjust the burner gas pressure only for natural gas Remove the cover screw Turn the regulator screw anti clockwise to decrease pressure or clockwise to incr...

Page 24: ...ter Ensure they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface Advise the person who is resuming responsibility that for continued safe operation the air heater should be serviced at least once a year SERVICING INSTRUCTIONS IMPORTANT Only appropriately qualified persons may carry out servicing and fault finding on this gas fired e...

Page 25: ...to remove all external dirt Check the security of the fan on the motor Note Fan motors are lubricated for life and do not require lubricating 4 Remove any dirt and or grease that may have accumulated on the venter fan motor and its housing Note The combustion air fan motors are lubricated for life and do not require oiling or greasing 5 The gas multi functional control valve requires no field main...

Page 26: ...operating instructions a copy of which is supplied with the air heater Fig 10b Fitting the ignitor 8 4 Multi functional gas control valve 1 Ensure gas supply to the air heater is turned OFF 2 After the air circulation fan has stopped switch OFF the electricity supply to the air heater 3 Mark for future identification and disconnect the wires connected to the valve 4 Disconnect the gas service unio...

Page 27: ...ricity supply to the air heater 3 To gain access to the fan open the hinged controls compartment access door refer to figure 9 for location 4 Mark for future identification and disconnect the wires connecting the fan motor at the terminals on the main wiring junction 5 Remove combustion air fan and clean as necessary using a wire brush and solvent to remove sticky residues 6 Re assemble and check ...

Page 28: ... dirty Determinewhat causedthe limit totrip Placeintonormal operation Check themains Check thetime tempeature control Is therecontinuitybetween 9 10 Is there230Vbetween 11 12 Is power ventingoperating Reset limit control Check venter motor Replacepressureswitch Isthethermostat above roomtemperatureandif usedisthetime clock ON Set thermostat aboveroom temperature if usedmake certainthetimeclock is ...

Page 29: ... pressure During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visible Check flame signal Is it greater than 1 0 micro Amps Check flame signal using micro amp meter Is signal greater than 1 0 micro Amps During 5 trial for ignition is a flame visible in ths view port Correct polarity Does the inlet gas pre...

Page 30: ...r distribution device been placed on the heater Is there excessive static pressure in the ductwork Did the motor overload trip Does the fan control energize the fan motor in less than 75 Adjust thermostat temp setting above ambient to energize fan gas solenoid valve Replace the motor Consult fan fault finding Does the limit trip before the fan is energized Place system in normal operation Consult ...

Page 31: ...RC 45 3 01 27202 ERP blower VRC 60 3 01 27203 ERP blower VRC 75 3 01 27204 ERP blower VRC 100 3 01 27205 Settings PARTS LISTING GAS CONVERSION VRC 3 air heaters are designed to operate on natural or propane gas and will be supplied fitted for the gas type ordered In the event of site conversion to a different gas type it is necessary to convert the gas burner and burner controls Affix new data pla...

Page 32: ...room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of the appliance and on a remote control if fitted Reset by pushing reset button inside the appliance or the remote control b check if thermal overheat control requires resetting 7 If the thermal overheat control...

Page 33: ...ing and itching of the skin Fiber entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling People with a history of skin complaints may be susceptible to irritation Dust levels are only likely when the material is abraded In general normal handling and use for this purpose will not present disc...

Page 34: ...irective Complies with the requirements of further directives namely GAD 2009 142 EC EMC 2004 108 EC LVD 2006 95 EC the following harmonized standards have been applied EN 1020 Non domestic gas fired forced convection air heaters for space heating not exceeding a net heat input of 300 kW incorporating a fan to assist transportation of combustion air and or combustion products The following notifie...

Page 35: ...1384 489 250 www ambirad co uk Registered in England N 1390934 Registered office 10 Norwich Street London EC4A 18D Nortek Global HVAC is a registered trademark of the Nortek Global HVAC Limited Because of continuous product innovation Nortek Global HVAC reserves the right to change product specification without due notice ...

Reviews: