1704VRC3-AMEN, p 3/35
INTRODUCTION
1.1
Basic
Information
The
instructions
in
this
manual
apply
to
Model
VRC
‐
3
gas
‐
fired/fan
‐
assisted
warm
air
heaters.
These
models
have
an
axial
fan
for
air
delivery.
These
heaters
are
designed
for
overhead
suspension
and
are
suitable
for
indoor
installation
only
installed
at
an
operation
ambient
temperature
between
‐
15°C
and
45°C.
When
installed
as
a
type
C12/C32
and
where
the
height
above
floor
level
is
greater
than
1,8
metres
measured
to
the
underside
of
the
appliance
they
may
be
used
as
a
garage
air
heater.
This
appliance
must
be
installed
in
accordance
with
the
rules
in
force.
Before
installation,
check
that
the
local
distribution
conditions,
nature
of
gas
and
pressure
and
adjustment
of
the
appliance
are
compatible.
A
permanent
electricity
supply
of
230
volts,
50
Hz,
single
phase
is
required.
Heaters
are
approved
for:
Type
C
12
‐
horizontal
vent
for
balanced
‐
flue
heaters;
Type
C
32
‐
vertical
vent
for
balanced
‐
flue
heaters;
Type
B
22
‐
vertical
vent;
Category
II
2H3
+
for
GB
and
IE
When
the
external
control
calls
for
heat,
an
electronic
control
begins
the
ignition
sequence
to
provide
for
a
safe
start.
About
30
seconds
after
the
call
for
heat,
the
fan
will
begin
circulating
warm
air.
The
electronic
control
will
supervise
the
flame
during
the
entire
heating
cycle
to
ensure
safe
operation.
When
the
required
room
temperature
is
reached,
the
main
burner
will
shut
down
leaving
the
fan
running
to
cool
down
the
heat
exchanger.
After
approximately
45
seconds,
the
fan
delay
relay
will
turn
off
the
fan.
1.2
Warranty
Warranty
is
void
if:
TECHNICAL
DATA
2.1
Specifications
Table
1
20
30
45
60
75
100
Gas category
Comb. Air & Flue Type B (1)
Comb. Air & Flue Type C (1)
Connection colars
mm
100
100
130
130
130
130
Heat inputs Hs
kW
26,42
31,63
54,38
73,25
87,85
114,87
Heat inputs Hi
kW
23,80
28,50
49,00
66,00
79,15
103,50
Heat output
kW
21,82
25,99
44,64
60,92
73,13
94,50
Thermal efficiency
%
91,70
91,20
91,10
92,30
92,39
91,30
Gas consumption G20
m3/h
2,52
3,02
5,19
6,98
8,38
11,19
Gas consumption G31
kg/h
1,86
2,22
3,82
5,15
6,17
8,24
Gas pipe connection (2)
inch
ESP MIN Press
Pa
50
50
50
100
150
100
ESP MAX Press
Pa
200
300
200
200
350
300
Air flow measured
m3/h
2248
2741
4023
5573
7079
8068
Temperature rise (3)
K
28
28
32
32
30
34
Electrical service (protection IP20)
400V 3P
50Hz
Blower electrical rating
W
660
1250
1410
1700
3070
3200
Total electrical rating
W
770
1370
1530
1810
3180
3320
Blower Weight
kg
14,5
20,5
27
26
41
45
Unit Weight
kg
54
55,8
87
99
109
155
Total Weight
kg
68,5
76,3
114
125
150
200
230/240V 1N 50Hz
230/240V 1N 50Hz
VRC-3
II2H3+
B22P
C12, C32, C42, C82
½"
¾"
a) VRC-3 heaters are installed in atmospheres containing flammable vapors or
atmospheres containing chlorinated or halogenated hydrocarbons or atmospheres
containing any silicone, aluminum oxide, etc., that adheres to spark ignition flame
sensing probes.
b) The installation is not in accordance with these instructions.
1
2
(1) Gas appliance Classifications for approved venting methods based on CEN report CR 1749:2001.
(2) There is a difference between the gas connection diameter and the diameter of the supply line. Always use the most adequate diameter of the supply line
to minimize the pressure drop through the gas pipes – if necessary, reduce the diameter of the supply line at the inlet of the unit.
(3) Figure for isothermal conditions.
Summary of Contents for VRC-3 100-3
Page 5: ...1704VRC3 AMEN p 5 35 VRC 30 3 VRC 45 3 ...
Page 6: ...1704VRC3 AMEN p 6 35 VRC 60 3 VRC 75 3 ...
Page 8: ...1704VRC3 AMEN p 8 35 VRC 30 3 with mix box VRC 45 3 with mix box ...
Page 9: ...1704VRC3 AMEN p 9 35 VRC 60 3 with mix box VRC 75 3 with mix box ...
Page 11: ...1704VRC3 AMEN p 11 35 VRC 30 3 with mix box and filters VRC 45 3 with mix box and filters ...
Page 12: ...1704VRC3 AMEN p 12 35 VRC 60 3 with mix box and filters VRC 75 3 with mix box and filters ...
Page 14: ...1704VRC3 AMEN p 14 35 2 5 Dimensions STANDARD UNIT ...
Page 15: ...1704VRC3 AMEN p 15 35 UNIT WITH MIXING CABINET option 526 ...