1704VRC3-AMEN, p 30/35
9.3
Limit
Control
Fault
Finding
Chart
(limit
control
trips)
Note
VRC
‐
3
air
heaters
are
equipped
with
2
limits
(a
recycling
limit
and
a
manual
reset
limit).
During
normal
operation,
neither
limit
should
trip
even
if
the
main
electric
supply
is
interrupted
during
operation.
In
the
event
of
motor
failure,
the
recycling
limit
will
trip
opening
the
gas
valve.
yes
no
yes
yes
no
yes
no
no
yes
yes
no
Check for excessive
main burner pressure
Does the fan
motor operate?
Remove the
restricition
Has any non-factory authorized air distribution
device been placed on the heater? Is there excessive
static pressure in the ductwork? Did the motor overload
trip?
Does the fan control
energize the fan motor
in less than 75"?
Adjust thermostat
temp. setting above
ambient to energize fan
& gas solenoid valve
Replace
the motor
Consult fan
fault finding
Does the limit trip
before the fan is
energized?
Place system in normal
operation
Consult fan
fault finding
Is there 220-240V at
terminals N and 4?
9.4
Fan
Fault
Finding
Chart
no
no
yes
yes
Adjust thermostat
temperature
setting above ambient to
energize the fan and the
fan solenoid valve
Does the fan
operate ?
Is there 220-240V
at terminals N & 4?
Replace the
fan start relay
Replace fan
motor
Place the system in
normal operation
Summary of Contents for VRC-3 100-3
Page 5: ...1704VRC3 AMEN p 5 35 VRC 30 3 VRC 45 3 ...
Page 6: ...1704VRC3 AMEN p 6 35 VRC 60 3 VRC 75 3 ...
Page 8: ...1704VRC3 AMEN p 8 35 VRC 30 3 with mix box VRC 45 3 with mix box ...
Page 9: ...1704VRC3 AMEN p 9 35 VRC 60 3 with mix box VRC 75 3 with mix box ...
Page 11: ...1704VRC3 AMEN p 11 35 VRC 30 3 with mix box and filters VRC 45 3 with mix box and filters ...
Page 12: ...1704VRC3 AMEN p 12 35 VRC 60 3 with mix box and filters VRC 75 3 with mix box and filters ...
Page 14: ...1704VRC3 AMEN p 14 35 2 5 Dimensions STANDARD UNIT ...
Page 15: ...1704VRC3 AMEN p 15 35 UNIT WITH MIXING CABINET option 526 ...