31
Base-2
Security Panel
ENGLISH
The Terminals
Power transformer [
26
]terminals (connected at Factory).
Open Collector Output terminals for the Alarm delay signalling. This Output
will be active during the Zone 1 “Delay”.
Open Collector Output for Trouble signalling. This Output is activated by the
following Trouble events:
Blown Peripheral fuse [
18
]
Blown Battery fuse [
19
]
Low battery
Reader Not Found
Short circuit on Reader wiring
Once the Trouble status has been cleared, Output, “
G
” will reset to standby
status within 30 seconds.
Outdoor peripheral terminals (HornStrobes, etc.)
Key/Card Reader terminals:
+/–
power supply terminals
C
Command terminal
R
Response terminal
Alarm Lines
Normally Closed
: the Line Inputs must be closed to Negative during
standby status
10K Balanced
: the Line Inputs must be closed to Negative during
standby
status, via a 10K
Ω
-¼W resistor
Power supply terminals to the devices connected to L1 and L2
The maximum current draw of terminals
+B
and
+F
must not exceed 400 mA DC.
24h Tamper Line terminals: these terminals must be closed to Negative during
standby status, via a 10K
Ω
-¼W resistor
Alarm Output: Relay 1 Free-Voltage Changeover terminals
Alarm Output for Indoor Sirens: Relay 2 Free Voltage Changeover terminals
During standby status, contacts NC1 and NC2 are closed to contacts COM1 and
COM2, respectively. During alarm status, contacts NA1 and NA2 will close to
contacts COM1 and COM2, respectively.
AC
PR
G
+B
M
M
M
M
M
BPI
L1 L2
+F
M
M
M
M
M
AS
M
M
M
M
M
NC1 NA1 COM1
NC2 NA2 COM2