c. Edit the file:
[INPUT_REGISTERS]
[HOLDING_REGISTERS]
REGISTER = 200,2,0134880000010041,2,3,1,0,0,0,0
REGISTER = 202,2,0134880000010041,2,4,1,0,0,0,0
REGISTER = 204,2,0134880000010041,2,5,1,0,0,0,0
REGISTER = ….
Where REGISTER = AAA,B,MMMMMMMMMMMMMMMM,C,D,E,F,G,H,I :
a. Navigate to the
Maintenance
section and select the
Modbus
tab.
b. Select
Upload Modbus File
and browse to the relevant Modbus configuration file.
c. Click on
OK
to upload the file.
d. After the upload is complete, click on
Activate Modbus
to apply the configuration.
For more details about TSAP ID, Object ID, Attribute ID, Index 1, and Index 2
values, see the following table or Ranger Pro User Guide.
e. The current Modbus configuration file can be downloaded by clicking on
Download
.
Table 4 - 2: Modbus Definitions and Settings
Location
Description
Setting
AAA
Offset from the first Modbus
Holding Register
(increments by B)
Modbus initial register address is 200
B
Data Size (word count)
Reserved (2)
MM...
EUI 64 Device ID
C
TSAP ID
TSAP is the device application processor
object ID for accessing process values.
TSAP (2) is the only supported
application object.
D
Object ID
Object ID refers to internal AIO objects.
o
3
: temperature
o
4
: Z acceleration
o
5
: Z velocity
o
6
: peakdemod
o
7
: Y accleration
32/46
Ranger Pro ISA100 Wireless Gateway
User Guide
158M1430 Rev. -