background image

FAULT LOCATION

Burner fails to start

Delayed ignition, burners starts violently

Burner fails to start after normal operation

Situation

Motor runs

Burner pre-purges

Flame occurs

Burner locks out

Motor runs

Burner pre-purges

No flame occurs

Burner locks out

Possible causes

Flame instability

Incorrect head settings

Low oil pressure

Excess air

Photocell not seeing light

Photocell failed

Control faulty

False light

No spark

No oil

Remedies

Check nozzle to burner head dimension 

and electrode position

Check oil pressure

Adjust air damper

Check that photocell is clean and 

unobstructed

Confirm with new photocell

Confirm with new control. (NB. it is 

advisable to change the photocell if also 

changing control)

Check that photocell is not seeing 

ambient light

Check that H.T. leads are sound and are 

not arcing other than at electrode gap

Check oil supply to burner - check that 

pump is not airlocked

Check operation of magnetic valve

Burner fails to start

Lamp not lit

Motor runs

 

Burner runs to lockout

Fuse has blown

Appliance thermostat has not reset

Appliance overheat device has operated

Control relay or photocell defective

No oil being delivered

Excessive flue draught is preventing 

 

flame establishment

No spark

Check or replace fuse if necessary. 

Check reason for failure

Adjust thermostat

Reset overheat device. Find reason for 

its operation and rectify

Check by replacement

Check that tank, oil lines, fire valve, pump 

and nozzle are all in good order

Rectify condition

Check ignition transformer. Check 

electrode gap and porcelain

Burner pulsates on start-up 

only with hot flue

Burner pulsates on start-up

Burner starts violently

Excessive draught

Nozzle partly blocked

Oil pressure too low

Flue blocked or damaged

Fan slipping on shaft

Pump coupling loose or worn

Delayed ignition

Adjust the burner

Replace nozzle

Check and adjust

Check and rectify

Check and retighten

Check and replace

Check the electrode adjustment, see 

diagram

Check electrodes for damage

Check H.T. leads for damage and 

disconnection

171 915 01  08-01

Summary of Contents for ST120KA

Page 1: ...178 009 15 Installation and maintenance instruction BENTOFLEX ST120KA...

Page 2: ...ables 5 Nozzle assembly 6 Nozzle 7 Brake plate 8 Blast tube 9 Ignition electrodes 10 Connecting pipe 11 Air damper 12 Solenoid valve 13 Pump 14 Drive coupling 15 Indication air damper 16 Fan wheel 17...

Page 3: ...utput range and nozzles recommended The net calorific value of 11 86 kWh kg for light oil has been used Burner tube Length of burner tube Incl flange A Measure B Incl flange B Measure B Incl flange C...

Page 4: ...TECHNICAL DATA 171 215 76 07 01 Flange A 10 3 25 130 150 89 7 Flange C 10 125 90 4 Flange D 125 150 10 3 90 5 12 Flange B 89 5 12 136 150 Dimensions...

Page 5: ...ombustion free of soot By this procedure an optimum adjust ment is obtained If larger nozzles are used the preadjustment of the air volume must be increased Condensation in chimney A modern burner wor...

Page 6: ...MAINTENANCE OF OIL BURNER Warning Before doing any service switch off power at the main switch and cut off the oil supply 171 305 68 07 01 Service of burner head and nozzle assembly...

Page 7: ...R1 Photoresistor S3 Main switch T1 Ignition transformer Y1 Solenoid valve X1 Plug in contact burner X2 Plug in contact boiler Outer electrical connection Mains connection and fuses in accordance with...

Page 8: ...d by means of the main switch or the thermostat a new start takes place when the conditions in accordance with point 1 are fulfilled The oil burner control cuts out A red lamp in the control is lit Pr...

Page 9: ...mercial quality according to current standards On commis sioning with an empty tube system the oil pump should not be run without oil for more than 5 min a condition is that the pump is being lubricat...

Page 10: ...stances the oil pressure falls below the set value andthevalveclosesagainstthe returnside R bymeansofthe diaphragm D andgoesintostarting position This can be remedied by Reducing the pump pressure Red...

Page 11: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Page 12: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Page 13: ...magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocell...

Page 14: ...B20 B30 B40 B45 02119815004 B50 B60 B70 B80 040588622001 B55 040588622002 B65 Enertech AB declares under sole responsibility that the above mentioned product is in conformity with the following stand...

Reviews: