30
Bentone
172 615 16 2018-01-15
7. Service
Whoever carries out service and maintenance on the burner must be
authorised to do so. If components need to be replaced, the replacements
must be of the same make and type and be approved by the authorities. If
the burner is to be used for a different grade of gas, a new adjustment must
be carried out. If town gas is to be used, it is also necessary to convert the
combustion assembly; in some cases the multi-block or valves and gas train
may also need to be changed to a larger type.
7.1 Servicing the combustion assembly
Removal and installation
1.
Switch off the main power supply and disconnect the Euro plugs from
the burner.
2.
Remove the cover and disconnect the ignition cable, ionisation cable
and control arm (D) from the gas nozzle.
3.
Loosen the nuts (B) and pull the burner body out of the guides.
4.
Loosen the screw (A); this releases the combustion assembly and
allows it to be lifted out.
5.
Check and clean the brake plate and gas inlet. If necessary, replace
the worn parts.
6.
Check the ignition electrode (see chapter Gas nozzle). Replace if
necessary.
7.
Check the ionisation electrode (see chapter Gas nozzle). Replace if
necessary.
8.
Fit the combustion assembly in reverse order.
9.
Press the burner together and lock using the nuts (B).
10. Fit the Euro plugs and turn on the main power supply.
11. Check/adjust the combustion.
!
If the burner is
directly connec-
ted, ensure that all
components on the
burner are without
power.
!
Check the gas
tightness.
G
G
G
Summary of Contents for 760000176601
Page 17: ...17 Bentone 4 10 Gas nozzle 45 Natural gas Propan Biogas UV detector ...
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...