14
Bentone
165 205 45
* Energy value of EO1 fuel oil = 11.86 kWh/kg
Burner output
30 kW
Estimated nozzle output:
30 / 11,86*
=
2,53 kg/h
Choice of nozzle according to the table (refer to Technical data).
According to the nozzle table, this provides the following nozzle.
Nozzle:
0,65 Gph
Pump pressure:
11,0 bar
4. Basic settings
4.1 Example of basic settings
4.1.1 Choice of nozzle
B 1 FUV
4.1.2 Basic settings
The setting value for 30 kW according to basic settings tables
(Setting values).
Air setting
=
12,5
Insert setting
=
5
Suction plate
=
4
Setting values for insert B 1 FUV
Setting values for air damper B 1 FUV
Nozzle assembly
, scale
Burner capacity, kW
0
2
4
6
8
10
12
14
15
20
25
30
35
40
45
Suction plate=4
Suction plate=1
Air
, scale
Burner capacity, kW
0
5
10
15
20
15
20
25
30
35
40
45
Suction plate=1
Suction plate=4