4.10 Setting values for nozzle assembly and
air damper B 40
Prior to commissioning, the basic settings of the burner can be set
in accordance with the diagram. See under Basic settings
Note that
it is simply a matter of a basic setting that should be adjusted
retrospectively once the burner has started.
A flue gas analysis and
soot quantity measurement must be carried out when fine-tuning the burner.
Recomended exsess air
Grade of Oil
Excess air flue gases
Max. % CO
2
% O
2
% CO
2
Lambda 1.2
Light oil, B10 heating oil/
biofuel blend (as defined in
DIN V51603-6)
3–5
≈12,5
15,4