24
Bentone
6.2 Servicing air dampers
Removal and installation
1.
Break the main current and disconnect the Euro plugs from the burner.
2.
Undo the nuts (E) and pull out the burner body on its guides.
3.
Remove the intake grille from the air intake.
4.
Release the damper motor.
5.
Clean the air damper (F) and the intake. Lubricate the damper shaft if
applicable.
6.
Re-engage the damper motor.
7.
Fit the intake grille over the air intake.
8.
Slide the burner together and secure it with the nuts (E).
9.
Connect the Eurostecker connectors and turn on the main power
switch.
10. Check combustion*.
E
F
Note:
*
When servicing/replacing components that affect combustion, an
analysis and soot test must be carried out on the installation
!
If the burner is directly connected, ensure that all components on
the burner are without power.