10. Oil burners maintenance instructions 

General information

Keep the boiler room clean. Ensure that the boiler 

room has permanent fresh air intake. Switch off before 

dismantling the oil burner. 

At hinged mounting, make sure that an automatic safety 

switch is fitted, so that the burner cannot start when 

theswing door is open. 

Don´t use the oil fired boiler to burn paper or 

rubbish,unless the boiler is especially fitted with a hinged 

door tomake this possible. 

Don´t fill tank while burner is working.

Starting precautions

Make sure that the oil tank is not empty 

Make sure that the valves on oil and water supply pipes 

areopen. 

Make sure that the boiler flue damper is open. 

Make sure that the boiler thermostat is set at the correct 

temperature. 

Switch on the current. Most relay systems have a 

delayed action so that the burner will not start for 

perhaps 20 seconds. 

With heavy oil the delay will be longer as the burner 

will notstart until the oil in the preheater reaches the 

requiredtemperature.

If the burner will not start

Press the reset button on the relay. Check that the 

thermostats are correctly adjusted. 

Don´t forget the room thermostat, check that any 

fusesare intact and main switch is on. 

If the burner starts but does not ignite

Make an attempt to start the burner. 

Never make close repeated start attempts. 

Don´t restart the burner until the boiler is free from oil 

gases. 

If the burner still does not ignite send for the service 

engineer.

When switching off during summer

Always use the main switch to cut out the burner even 

when adjusting the burner or cutting off the heating for 

ashort time. For longer periods of shut down, close all 

valves and the oil supply stop-cock. 

Clean the filter and nozzle by washing in petrol or 

paraffin. 

Make sure the filter medium is not damaged or defective. 

Protect electrical gear from damp.

Warning

Never stand too near or put your face to the inspection 

or fire door, when the burner is about to start. 

Never use a naked flame to ignite oil if the electrical 

ignition fails. 

Always wait for about 10 minutes for the unburnt gases 

to disperse before restarting the oil burner if it has failed 

to ignite previously.

Installed by: 

Tel:

Summary of Contents for Bentoflex ST 133 K

Page 1: ...Providing sustainable energy solutions worldwide 178 109 17 1 2019 09 19 Installation and maintenance instruction ST 133 K10K CN...

Page 2: ...2 Bentone...

Page 3: ...15 5 Burner servicing ____________________________________ 18 5 1 Servicing _______________________________________ 18 5 2 Servicing the combustion device ___________________ 18 5 3 Replacing the oil...

Page 4: ...elative humidity no condensation Temperature 20 to 60 C Check that the burner is compatible with the boiler s output range The label information on the rating plate refers to the burner s minimum and...

Page 5: ...tch this must be equipped with a hatch opening switch connected to the burner s safety system When in operation the burner s noise level can exceed 85 dBA Use hearing protection The burner must not be...

Page 6: ...h Change cleaning Brake plate 1 Year Change cleaning 3000h Change cleaning Motor 1 year 3000 hrs Cuppling chaft 1 year control change 3000h control change Fan wheel 1 Year Change when dirty unbalance...

Page 7: ...il B10 heating oil biofuel blend as defined in DIN V51603 6 and is used for Water heating generators Hot air generators these require LMO 24 255 C2E 2 1 Dimensions ST 133 Min recommended distance to f...

Page 8: ...Flange 1 d1 d 2 d 3 Combustion device d1 d2 d3 ST 133 90 M10 125 150 2 3 Burner installation 2 3 1 Hole patten Make sure the hole pattern on the boiler is designed for burner flange Length of blast t...

Page 9: ...lete burner Sound ST 133 K 125W 0 95A 230V 50 60Hz 4 F 230V 0 8A 50Hz 74 dBA 0 5 dBA ST 133 KV 125W 0 95A 230V 50 60Hz 4 F 230V 1 0A 50Hz 74 dBA 0 5 dBA 2 5 1 Electric Specification Burner correspond...

Page 10: ...0 39 3 42 40 0 85 2 83 33 3 00 36 3 16 37 3 32 39 3 47 41 3 61 43 3 74 44 3 87 46 1 00 3 33 39 3 53 42 3 72 44 3 90 46 4 08 48 4 24 50 4 40 52 4 56 54 1 10 3 66 43 3 88 46 4 09 48 4 29 51 4 48 53 4 67...

Page 11: ...tion cables 5 Nozzle assembly 6 Nozzle 7 Brake plate 8 Blast tube 9 Ignition electrodes 10 Connecting pipe 11 Air damper 12 Solenoid valve 13 Pump 14 Drive coupling 15 Indication air damper 16 Fan whe...

Page 12: ...ot pinched or otherwise damaged during installation or servicing 3 1 1 Installation and Maintenance Manual The maintenance instructions supplied with the burner must be kept at an easily accessible lo...

Page 13: ...ected to tensile stresses or become excessively bent when the burner is swung out or removed for servicing The oil filter should be installed so that the filter cartridge can easily be replaced or cle...

Page 14: ...of the oil filter 3 For single pipe systems the return plug must be removed refer to Pump instructions 4 When installing oil hoses check that the supply and return hoses are fitted to the appropriate...

Page 15: ...26 ST 133KV 76 26 Burner output 70 kW Output calculation due to preheater for nozzle choice according to the table refer to Technical data Estimated nozzle output 70 x 1 06 74 2 kW 74 2 11 86 6 25 kg...

Page 16: ...16 Bentone Air Insert scale Setting values for insert ST 133K KV Setting values for air damper ST 133K KV 0 5 10 15 20 25 30 35 10 61 77 4 97 9 119 9 0 5 10 15 20 25 10 61 77 4 97 9 119 9...

Page 17: ...position affects airflow Therefore it is always necessary to fine tune airflow using the burner s airflow regulator 4 1 4 Air intake adjustment Setting the air intake is very important to achieve goo...

Page 18: ...off mains power and disconnect the Europlug from the burner 2 Remove the burner from the boiler by loosening the screw A 3 Loosen the housing screw B and remove the front cover C 4 Visually inspect t...

Page 19: ...pump 5 Disconnect the solenoid valve cable from the pump 6 Disconnect the connection tube D from the pump 7 Loosen the screws E and pull out the oil pump 8 Install the new oil pump on the burner Tigh...

Page 20: ...eel 9 Fit the fan wheel to the motor tighten the locking screw The fan wheel must be fitted with a little play between the motor and the fan wheel Make sure that there are no scratching noises Refit t...

Page 21: ...witch on mains power start the burner and check the combustion 5 6 Replacing the entire electrical package 1 Switch off mains power and disconnect the Europlug from the burner 2 Remove the burner from...

Page 22: ...emove the burner control and loosen the two bottom screws in the relay socket 4 The Europlug plate is firmly attached under the relay socket 5 Remove the cable of the component to be replaced 6 Connec...

Page 23: ...240V 50 60 Hz Oil temperature max 60 C Components 1 Suction line G 1 4 2 Return line G 1 4 and internal by pass plug 3 Nozzle outlet G 1 8 4 Pressure gauge port G 1 8 5 Vacuum gauge port G 1 8 6 Pres...

Page 24: ...by pass channel between the pressure and return sides of the valve is open No pressure will then be built up to open the valve it does not matter which speed the gear set has When the solenoid is acti...

Page 25: ...38 1 2 18 61 150 2 3 22 73 150 3 4 26 85 150 4 4 30 97 150 11 38 96 150 7 27 71 150 20 54 116 150 16 46 100 150 12 42 107 150 8 31 79 150 23 61 130 150 19 52 112 150 13 47 118 150 9 34 88 150 26 68 14...

Page 26: ...lculated values where the pipe dimensions and oil velocity have been matched so that tur bulences will not occur Such tur bulences will result in increased pressure losses and in acoustic noise in the...

Page 27: ...the burner and check seals and combustion Use caution when operating the burner surfaces may be hot When servicing oil bearing components check for oil leakage when the burner is commissioned after s...

Page 28: ...gasket seal pump Removal and installation 1 Disconnect hoses oil pipes and electrical cables 2 Loosen the pump screw J 3 Loosen the gasket seal s locking rings 4 Remove the old gasket seal 2 5 Install...

Page 29: ...29 Bentone 165 105 31 7 Oil burner control 7 1 Wiring diagram Mains connection and fuses in accordance with local regulations A DC Bl Svart LMO QRB 12 11 Blue Blau Bleue Black Schwarz Noir A1...

Page 30: ...rol 3 a b The safety time expires If no flame is established before this time limit the control cuts out If for some reasons the flame disappears after this time limit the burner will make an attempt...

Page 31: ...sed the problem by pressing and holding the reset button for 3 seconds The number of flashes below is repeated with a pause in between 2 flashes No flame signal when safety time expires 4 flashes Fals...

Page 32: ...nt light Check high voltage wiring and ignition electrodes Check preheater function Symptom Burner does not start Burner pre ventilates Burner stops Causes Fuse blown Boiler thermostat has not reset P...

Page 33: ...ght Adjust the burner Check preheater function Adjust the preheater s set operating temperature Ensure that the new oil s physical parame ters are within the limits for which the burner is designed If...

Page 34: ...171 905 28...

Page 35: ...Address Test performed by Postal address Company name Tel no Boiler Type Make Power kW Bentone Burner Type Model Serial no Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke nu...

Page 36: ...perature If the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main swi...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Reviews: