15
Bentone
165 205 31
4. Basic settings
4.1 Example of basic settings
4.1.1 Choice of nozzle
ST 146 B30A
Burner output
70 kW
Estimated nozzle output:
70 / 11.86*
=
5,90 kg/h
Choice of nozzle according to the table (refer to Technical data).
According to the nozzle table, this provides the following nozzle.
Nozzle:
1,50 GPH
Pump pressure:
11.0 bar
ST 146 B30A
Burner output
70 kW
Output calculation due to preheater for nozzle choice according to the table
(refer to Technical data).
Estimated nozzle output:
70 x 1.06
=
74,2 kW
74,2/11.86 *
=
6,25 kg/h
Choice of nozzle according to the table (refer to Technical data).
According to the nozzle table, this results in the following nozzle.
Nozzle:
1,65 GPH
Pump pressure:
10.5 bar
4.1.2 Basic settings
The setting value for 70 kW according to basic settings tables
(Setting values).
Air setting
=
9.0
Insert setting
=
8.0
* Energy value of EO1 fuel oil = 11.86 kWh/kg