23
Bentone BFG1
D
M
4.4.4 Inlet cone, air control
The air flow is also affected by the position of the intake cone. This rarely
needs adjustment, however, and should be maintained in the standard
position ”STD” for good operation and starts. (A cast-in arrow on the fan
housing indicates the position of the inlet cone. In addition to the scale on
the inlet cone casting, there is also a mark (M) indicating the factory setting.)
4.4.5 Rotation of air intake
The air intake can be rotated in order to fit the burner into different
environments. The intake can be rotated into various positions, not just the
ones shown to the left.
To rotate the air intake, loosen the three screws securing the air intake and
the two screws fastening the air pressure switch. Then rotate the air intake to
the desired position and tighten the screws.
The air intake position does somewhat affect the air flow through the burner.
The position giving the largest flow is with the air intake downwards.
4.4.6 Air duct
A hose connection via a air duct is available in three different dimensions, 48,
68 and 78 mm outer diameter ”D”. The air duct is installed on the air intake
at the place where the grid is installed in the standard design.