19
General
Adjustment of outlet pressure (setpoint adjustment)
Factory setting: Standard spring p2 10-30 mbar
1.
1.
Unscrew protective cap A.
2.
Adjustment (+) Setting spindle B ”Turn counter-
clockwise” = Increasing outlet pressure (setpoint)
3.
4.
1.
B
A
2.
B
B
E
C/D
B
A
2.
Adjustment (-) Setting spindle B
”Turn clockwise” = Reducing outlet pressure (setpoint)
1.
Check setpoint
2.
Screw on protective cap A.
3.
Attach lead seal (Page 5).
Replace setting spring
3-4
1.
Remove protective cap. A.
Release spring by turning
adjustment spindle B counter
clockwise. Turn spindle to stop.
2.
Unscrew complete adjustment
device B and remove spring C.
3.
Insert new spring D.
4.
Assemble complete adjustment
device and adjust desired off-
set.
5.
Screw on protective cap A.
Stick adhesive label E onto
typplate.
6.
Attach lead seal.
or