23
General
4.2.1.3 Alarm code table
Red blinking code
on
signal lamp (LED)
Possible causes
Blinking 2 x
..
No flame creation at End of “TSA”
- defective or fouled flame monitoring
- defective or fouled fuel valves
- poor burner setting
- defective firing device
Blinking 3 x
...
“LP” defective
- No air pressure switch signal after “t10”
- “LP” is welded in open position
Blinking 4 x
....
Illegal flame signal during start-up
Blinking 5 x
.....
Time out “LP”
- “LP” is welded in open position
Blinking 6 x
......
Free
Blinking 7 x
.......
Too many flame disappearances during operation
- poor burner setting
- defective or fouled fuel valves
- defective or fouled flame monitoring
Blinking 8 x
........
Free
Blinking 9 x
.........
Free
Blinking 10 x
..........
Connection fault or internal fault, outgoing contacts
or other faults
Blinking 14 x
..........
....
CPI contact not closed
During the diagnosing of the alarm cause, the control outputs are voltage-
free.
• The burner is disconnected
• Exception, alarm signal «AL» at board 10
• Reconnection of the burner happens after resetting only.
• Press the reset button 0.5...3 s
4.2.1.4 Interface diagnostics
To change to interface mode, press and hold the reset button longer than
3 s. To go back to the normal position, press and hold the reset button
longer than 3 s. If the gas burner control is in the alarm position, it is reset by
pressing the reset button 0.5...3 s.
Summary of Contents for BFG1
Page 2: ......
Page 8: ...8 General 1 1 Description BFG1 7 8 10 11 12 13 14 15 16 22 1 2 3 4 5 6 24 23...
Page 11: ...11 General 7 8 10 9 1 2 3 5 6 12 4 2 1 Description STG 23 24 16...
Page 20: ...20 General 4 ELECTRIC EQUIPMENT LME 4 1 Wiring diagram Alt 1 Enl DIN 4791 Alt 2 Alt 3...
Page 24: ...24 General...
Page 25: ...25 General...
Page 26: ...26 General...
Page 27: ......
Page 28: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...