4.7 Inspection of gas nozzle before
commissioning
General rules
Care should be taken by the installer to ensure that no electrical cables
or fuel/gas pipes are trapped or damaged during installation or service/
maintenance.
Gas nozzle
Check that the ignition and ionisation electrodes are correctly set. In
the figure (see the gas nozzle chapter), the dimensions are specified for
adjustment of the ignition and ionisation electrodes.
Gas quality
Ensure that the burner head is meant for the gas quality to be used (see
capter gas nozzle).
De-aerating
De-aerating of the gas line is conducted, for example, by unscrewing
the screw on the measuring nipple for the connection pressure. Connect
a plastic hose and release the gas in a safe place. Once de-aerating is
completed, be sure to refit the screw on the measuring nipple.
Leakage control
When making a leakage control of the gas supply system the solenoid valve
should be closed. Connect a pressure gauge to the test nipple Pa, see fig.
The test pressure in the system should be 1,5x max. inlet pressure or min.
150 mbar. If any leakage, locate the source by means of soapy water or a
leak location spray. After tightening repeat the test.
Electric function test:
Ensure that phase and neutral are not reversed. The gas shut-off cock
should be closed.To prevent the gas pressure switch from locking out it
should be linked temporarily.
After the main switch has been switched on and the thermostats have been
adjusted the pre-purging period begins (30-35sec.). At the end of this period
the pre-ignition period starts (0,5-2,5 sec. dependent on the design of the
gas control). The gas valve is energized and opens and flame is established.
At the end of the safety time (2-3 sec.) the gas control locks out. The
solenoid valve and the motor will be "dead". Remove the link from the gas
pressure switch after the test is finished.
Note on 2-stage and modulating burners that during the pre-purging period
the damper opens to the set value for air on stage 2 and just before the
end of the pre-purging period it goes down to the air setting for stage 1. On
some burners under 350kW the pre-purging mainly takes place with the air
damper set for stage 1.
!
If the burner is
directly connected,
ensure that all
components on
the burner are
without power.