18
Bentone
General instructions
The installation of the gas burner must be carried
out in accordance with current regulations and
standards. The installers of gas burners should
therefore be acquainted with all regulations and ensure
that the installation complies with the requirements. The
installation, mounting and adjustment should be made
with the greatest care and only the correct gas should be
used.
Operating instructions
The installation and maintenance instructions supplied
with the burner must be kept at an easily accessible
location in the boiler room.
Instructions
The user should be thoroughly in-structed in the function
of the gas burner and the whole installation. The supplier
must instruct the user.
Inspection and maintenance
Inspection as needed, preferably daily. Maintenance per
service schedule.
Start up
After the burner has been fitted to the boiler and the
electric connection, the leakage control, the venting
and the electric function test have been carried out, the
burner will be ready for start-up.
Howerer, study the sections dealing with adjustments of
multi-bloc, combustion air and combustion head.
Open the ball valve and switch on the main switch. If the
burner starts the actual adjustment can be made.
Adjustment of burner head
The burner is equipped with an adjustment device
changing the po si tion of the brake plate in the burner
head. This is used to adjust the cor rect pressure drop
over the com bus tion device in order to obtain a good
pulsation free combustion.
Which position to use depends on input and
overpressure in the boiler.
A general rule is that the lower capacity the smaller the
opening between brake plate and combustion device.
Commissioning of installation
Control of the combustion. The combustion quality is
checked by means of a flue gas analysis device. Adjust
the burner to appr. 20% excess air in accordance with
the table. Check the flue gas temperature. Calculate the
efficiency. Check also the actual gas volume on the gas
meter so that the correct input is achieved
Service
Service should only be carried out by qualified personnel.
Replacement parts should be of the same make and
approved by the same authorities as the original. If the
burner is converted to fire another gas quality it must
be re-commissioned. If town gas is to be fired the
combustion head must be converted and the gas train
adjusted to suit (e.g.a larger gas armature or a different
spring in the governor may be required).
Gas quality
CO
2
%
lambda 1,2
0
2
%
max. CO
2
%
Natural gas
10,0
4±1
11,9
LPG
11,5
4±1
13,9
Summary of Contents for BG400M
Page 15: ...15 Bentone 172 515 08 2018 01 02 4 8 Gas nozzle Natural gas Propan Biogas UV detector 2 5 8 0 ...
Page 35: ...35 Bentone 10 2 Wiring diagram LME ...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...