Cause of fault
Action
CO content too high:
Surplus air when using natural gas and liquefied petroleum
(propane, butane).
Choke the air supply.
Poor air supply.
Open the air supply. Check flue gas damper.
Holes in gas nozzle clogged.
Clean.
Poor fresh air intake.
Check and increase.
Flame at incorrect angle due to combustion head out of position.
Check the combustion head and readjust.
Condensation build up in boiler and chimney:
Flue gas temperature too low or gas volume too low.
Raise the flue gas temperature by increasing
gas volume Insulate the chimney.