8
Bentone
2.2 Capacity range
2.3 Gas categories, approved gases
Only dry gas is permitted for use.
Capacity kW
Gas quantity
at min. power
Nm
3
/h
1
)
Gas quantity
at max. power
Nm
3
/h
1
)
Max.
connection
pressure
mbar
Min connection
pressure mbar
see data plate
1
) Lower heat value Hu at normal state 15°C and 1013.25 mbar EN676
Grade of gas
Natural gas
Natural gas
Butane
Propane
Gas quantity and capacity vary according to grade of gas and connection
pressure.
BG 400-2, BG 400 M
G20 61-325
6.4
34,2
360
G25 61-310
7.4
37,8
360
G30 61-350
1,9
10,5
360
G31 61-340
2,5
14,2
360
kWh/Nm
3
MJ/Nm
3
kcal/Nm
3
G20
9.5
34.02
8126
G25
8.2
29.25
6986
G30
32.5
116.09
27728
G31
24.6
88.00
21019
Summary of Contents for BG400M
Page 15: ...15 Bentone 172 515 08 2018 01 02 4 8 Gas nozzle Natural gas Propan Biogas UV detector 2 5 8 0 ...
Page 35: ...35 Bentone 10 2 Wiring diagram LME ...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......