FS
lights red
Light period (waiting time 10 s)
Flash code
Paus
Flash code
c:a 3 s
Press reset-
button > 3 s
9.2 Control program when disruption;
Disruption display, Gas burner control: LME....
Colour codes
Colour code table for multi-coloured signal lamps (Light diodes)
Status
Colour codes
Colours
Waiting time «tw», other waiting times
○…………………
Off
Ignition phase, ignition checked
•
○
•
○
•
○
•
○
•
○
•
Flashing yellow
Normal operation
□…………………
Green.
Operation, poor flame signal
□○□○□○□○□○
Flashing green
Prohibited flame signal during start up
□▲□▲□▲□▲□▲
Green-Red
Undervoltage
●▲●▲●▲●▲●▲
Yellow-Red
Disruption, alarm
▲…………………
Red.
Flashing code for fault codes
▲○ ▲○ ▲○ ▲○
Flashing red
Interface diagnostics
▲▲▲▲▲▲▲▲
Red flickering
Diagnostics alarm trigger
The red alarm signal lamp lights continuously after the alarm is disconnected.
Diagnostics for alarm triggers can be read as specified by the following
sequence:
......
Continuous
Off
▲
Red
●
Yellow
□
Green
7.2.1.2 Limiting of starting repetitions
LME ... has a function with start repetition if the flame is not created at start ord disappears during operation.. LME ...
allows max. three repetitions during coninuous starting cycle