Par
.
no.
Par
ameter
Number of
elements
T
ype
Edit
V
alue r
ange
Min Max
Reso-
lution
Default
setting
Passwor
d le
vel
942
Active load sour
ce
1 = output during curve settings
2 = manual output
3 = default output via building automation
4 = default output via analog input
5 = e
xternal load contr
oller via contacts
1
Selection
read only
0
255
1
0
SO
947
Result of contact sensing (bit-coded)
Bit 0.0 = 1: Pr
essur
e switch-min
Bit 0.1 = 2: Pr
essur
e switch-max
Bit 0.2 = 4: Pr
essur
e switch valve pr
oving
Bit 0.3 = 8: Pr
essur
e switch air pr
essur
e switch
Bit 0.4 = 16: Load contr
oller OPEN
Bit 0.5 = 32: Load contr
oller ON
Bit 0.6 = 64: Load contr
oller CL
OSE
Bit 0.7 = 128: Safety loop
Bit 1.0 = 1: Safety valve
Bit 1.1 = 2: Ignition
Bit 1.2 = 4: Fuel valve 1
Bit 1.3 = 8: Fuel valve 2
Bit 1.4 = 16: Fuel valve 3 / pilot valve
Bit 1.5 = 32: Reset
2
Std_u8
read only
0
255
1
0
Info / Service
948
Contact feedback network counter r
egister
14
Std_u8
read only
0
255
1
0
SO
950
Requir
ed r
elay state (bit-coded)
Bit 0 = 1: Alarm
Bit 1 = 2: Safety valve
Bit 2 = 4: Ignition
Bit 3 = 8: Fuel valve 1
Bit 4 = 16: Fuel valve 2
Bit 5 = 32: Fuel valve 3 / pilot valve
1
Std_u8
read only
0
255
1
0