Err
or code
Diagnostic code
Meaning for the LMV37.4... system
Remedy
no Comm
No communication between LMV37.4... basic unit and AZL2...
Check wiring for line interruption/loose contact
2
#
No flame at the end of the safety time (TSA)
1
No flame at the end of safety time 1 (TSA1)
2
No flame at the end of safety time 2 (TSA2)
4
No flame at the end of safety time 1 (TSA1) (softwar
e version
≤
V02.00)
3
#
Air pr
essur
e failur
e
0
Air pr
essur
e off
1
Air pr
essur
e on
2
Evaluation of air pr
essur
e
Corr
ect the setting of par
ameter 235 or 335
(Deactivation of the air pr
essur
e check in oper
ation only allo
wed in pneumatic
oper
ation!)
4
Air pr
essur
e on – start pr
evention
20
Air pr
essur
e, combustion pr
essur
e – start pr
evention
68
Air pr
essur
e, POC – start pr
evention
84
Air pr
essur
e, combustion pr
essur
e, POC – start pr
evention
4
#
Extr
aneous light
0
Extr
aneous light during startup
1
Extr
aneous light during shutdo
wn
2
Extr
aneous light during startup – start pr
evention
6
Extr
aneous light during startup, air pr
essur
e – start pr
evention
18
Extr
aneous light during startup, combustion pr
essur
e – start
pr
evention
24
Extr
aneous light during startup, air pr
essur
e, combustion pr
essur
e –
start pr
evention
66
Extr
aneous light during startup, POC – start pr
evention
70
Extr
aneous light during startup, air pr
essur
e, POC – start pr
evention
82
Extr
aneous light during startup, combustion pr
essur
e, POC – start
pr
evention
86
Extr
aneous light during startup, air pr
essur
e, combustion pr
essur
e,
POC – start pr
evention
11.
Err
or code list
Summary of Contents for STG 146i/2