Err
or code
Diagnostic code
Meaning for the LMV37.4... system
Remedy
132
#
Internal err
or EEPROM r
egister initialization
Make a r
eset; if err
or occurs r
epeatedly
, r
eplace the unit
133
#
Internal err
or EEPROM access – Request synchr
onization
Make a r
eset, r
epeat last par
ameterization / c
heck. If err
or occurs r
epeatedly
,
replace the unit
134
#
Internal err
or EEPROM access – Request synchr
onization
Make a r
eset, r
epeat last par
ameterization / c
heck. If err
or occurs r
epeatedly
,
replace the unit
135
#
Internal err
or EEPROM access – Request synchr
onization
Make a r
eset, r
epeat last par
ameterization / c
heck. If err
or occurs r
epeatedly
,
replace the unit
136
#
Restor
e
1
Restor
e started
Restor
e of a backup has been started (no err
or)
Ne
w de
vices r
equir
e r
esetting follo
wing r
estor
e!
for further diagnostic codes for err
or code 136, r
efer to err
or
code 137
For measur
es, r
efer to err
or code 137
137
#
Internal err
or – backup / r
estor
e
157 (-99)
Restor
e – ok, but backup < data set of curr
ent system
Restor
e successful, but backup data se
t is smaller than in the cur
rent system
239 (-17)
Backup – stor
age of backup in AZL2... faulty
Make r
eset and r
epeat backup
240 (-16)
Restor
e – no backup in AZL2...
No backup in AZL2...
241 (-15)
Restor
e – interruption concerning unpassable ASN
The Backup has a unpassable ASN and may not
restor
e of the unit
242 (-14)
Backup – backup made is inconsistent
Backup is faulty and cannot be tr
ansferr
ed back
243 (-13)
Backup – data comparison between µCs faulty
Repeat r
eset and backup
244 (-12)
Backup data ar
e incompatible
Backup data ar
e incompatible with the curr
ent softwar
e version, r
estor
e not
possible
245 (-11)
Access err
or to par
ameter Restor
e_Complete
Repeat r
eset and backup
246 (-10)
Restor
e – timeout when storing in EEPROM
Repeat r
eset and backup
247 (-9)
Data r
eceived ar
e inconsistent
Backup data set invalid, r
estor
e not possible
248 (-8)
Restor
e cannot at pr
esent be made
Repeat r
eset and backup
249 (-7)
Restor
e – abortion due to unsuitable burner identification
Backup has an unsuitable burner ide
ntification and must not be
transferr
ed to
the unit
250 (-6)
Backup – CRC of one page is not corr
ect
Backup data set invalid, r
estor
e not possible
251 (-5)
Backup – burner identification is not defined
Define burner identification and r
epeat backup
252 (-4)
After r
estor
e, pages still on ABORT
Repeat r
eset and backup
253 (-3)
Restor
e cannot at pr
esent be made
Repeat r
eset and backup
254 (-2)
Abortion due to tr
ansmission err
or
Repeat r
eset and backup
255 (-1)
Abortion due to timeout during r
estor
e
Make a r
eset, check the connections and r
epeat the backup
Summary of Contents for STG 146i/2
Page 34: ...34 Bentone 6 2 Wiring diagram...
Page 123: ......
Page 124: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...