21
Bentone
4.8
Setting the gas pressure switch max/
overload protection switch
!
Check the gas tightness.
172 535 17-3
The gas pressure switch must react to excessive gas pressure in the
burner. Start can only be done by manual reset (gas burner control or
overpressure switch).
The switch blocks the burner if gas pressure between gas valve and
burner becomes too high. The overload protection switch can be
connected so that it provides automatic restart or that the burner is
blocked, see S10 or S16 in the wiring diagram. The system’s safety
regulations control connection options.
1.
Remove protective cover.
2.
Open measuring socket and connect a manometer for
measuring connection pressure.
3.
Start the burner.
4.
Measure and note the highest gas pressure in the entire work
area.
5.
Set the gas pressure switch to a value 10-15% lower than the
noted pressure.
6.
Test run the burner and check the function in the entire work
area.
7.
Remove manometer and close measuring socket.
8.
Refi t protective cover.