28
Bentone
!
When servicing/replacing components that aff ect combustion,
fl ue gas analysis and soot test shall be carried out on the installation.
5.3
Air intake and intake cone
1.
Switch off the main power supply and turn off the gas.
2.
Remove gas line by loosening the electrical cabling and
screws to the gas valve and lift out.
3.
Loosen screws and lift burner out of fi xing fl ange.
4.
Remove air intake and fl ame tube.
5.
Disconnect ignition cable.
6.
Disassemble the burner by loosening the through screw (K)
and removing the front piece.
7.
Check function and appearance of the various components
included in the air control. Clean and replace components if
necessary.
8.
Mount the burner in reverse order. Be sure to mount
components in the same position as when disassembling.
9.
Turn on the main power and open the gas fl ow.
10. Start burner and check/adjust combustion.
!
Check gas tightness.
K
160303-514
160303-515
!
Before obtaining access to terminals,
all supply circuits must be disconnected.
Summary of Contents for STG 146i/2
Page 34: ...34 Bentone 6 2 Wiring diagram...
Page 123: ......