32
Bentone
172 615 88 2021-11-07
Control system
10 years
250,000 starts
Valve control system
10 years
250,000 starts
Pressure switch
10 years
250,000 starts
Ignition system with flame guard 10 years
250,000 starts
UV flame sensor
10,000 h
N/A
Gas pressure controls
15 years
N/A
Gas valve without seal testing
10 years
250,000 starts
Gas valve with seal testing
Replacement upon fault detection
N/A
Gas pressure switch
10 years
250,000 starts
Safety blow-off system
10 years
N/A
Damper motor
N/A
500,000 starts
Contactor
10 years
500,000 starts
Burner
1 year
3,000 h
Inspection of electrical
installation
1 year
3,000 h
Tightness check
1 year
3,000 h
Filter
1 year, replacement at Δp>10 mbar 3,000 h, replacement at Δp>10 mbar
Electrodes
Replacement/cleaning 1 year
Replacement/ceaning 3,000 h
Brake disc
Replacement/cleaning 1 year
Replacement/ceaning 3,000 h
Motor
1 year
3,000 h
Fan wheel
1 Year
Replace if need for cleaning/
imbalance
3,000 h
Replace if need for cleaning/
imbalance
The burner and its components must be recycled according to applicable regulations.
5.8
Burner Service Schedule, Gas
Servicing must be carried out once a year or after 3,000 hours of operation.
5.9
Component replacement intervals
Summary of Contents for STG 146i/2