7.13 Display diSP
By configuring the position of the decimal point and automatic
changeover (timer), both LED indications can be adapted to the
respective requirements. Timeout tout for operation and the locking
of levels can be configured as well.
ConF
dISP
Parameter
Value/
selection
Description
Upper display
diSU
Upper display
0
1
4
6
7
Display value for upper display
Switched off
Analog input InP1
Controller’s angular positioning
Setpoint
End value with thermal shock protection
Lower display
diSL
Lower display
0
1
4
6
7
Display value for lower display
Switched off
Analog input InP1
Controller’s angular positioning
Setpoint
End value with thermal shock protection
Timeout
tout
0...
180
...
255
Time (s) on completion of which the controller returns automatically to
the basic display, if no button is pressed.
Decimal point
dECP
Decimal point
0
1
2
No decimal place
One decimal place
Two decimal places
If the value to be displayed cannot be shown with the programmed
decimal point, the number of decimal places is automatically reduced.
If the measured value drops again, the number of decimal places is
increased until the programmed value is reached
Locking of levels
CodE
0
1
2
3
No locking
Locking of configuration level
Locking of parameter level
Locking of keyboard