8.2 General information
The burner management system is operated and parameterized via
the AZL2… display. The AZL2… with LCD and menu-driven operation
facilitates straightforward use and targeted diagnostics. When
making diagnostics, the display shows the operating states, the type
of error and the point in time the error occurred. Passwords protect
the different parameter levels of the burner against unauthorized
access. It is possible to select from different types of fuel trains and
make use of a wide choice of individual parameter settings (program
times, configuration of inputs / outputs, etc.), enabling the installer to
make optimum adaptations to the relevant application. A change of
parameters varies in levels of authorization, this manual will give info
on those that might be changed by the installer. The actuators are
driven by stepper motors and can be positioned with high resolution.
Specific features and actuator settings are defined by the LMV37.4...
basic unit.
8.3
Technical Data Basic unit LMV37.4...
Mains voltage
LMV37.400A2
AC 230 V -15 % / +10 %
Mains frequency
50 / 60 Hz ±6 %
Safety class
I, with parts according to II and III
to DIN EN 60730-1
Perm. mains primary fuse
(externally)
Max. 5 AT
Unit fuse F1 (internally)
6.3 AT (DIN EN 60127 2 / 5)
Mains supply: Input current
depending on the operating state
of the unit
Under voltage
Safety shutdown from operating
position at mains voltage
LMV37.400A2
Approx. AC 186 V
Restart on rise in mains voltage
LMV37.400A2
Approx. AC 195 V