69
Bentone
P
V
h
s min %
Bi
ld
1
0
1
/0
8
0
7
Parameter
641
to control speed standardization
of the VSD.
Choose:
0 = speed standardization of VSD OFF
If the parameter is set correctly, move directly to the next parameter with
+
Press:
/reset
to adjust parameter
641
: speed standardization
Select your setting by pressing one of the buttons
-
+
Press:
/reset
to save the setting for parameter
641:
VSD
Press:
ESC
-
+
to return to parameter level.
Go to the next parameter with
+
P
V
h
min s
%
Bi
ld
1
0
2
/0
7
0
7
Display
P0
appears flashing.
Fuel/air settings are not made in the display but
on the respective component on the burner, see
chapter "Burner settings".
Go to P9 with
+
P
V
h
min s
%
Bi
ld
1
1
2
/0
7
0
7
Display
P9
appears flashing.
Press
+
to start the burner.
P
V
h
min s
%
Bi
ld
1
1
3
/0
7
0
7
Identification of start for setting the curve
parameters.
Press
/reset
to continue.
The burner motor will then start and a number of phases in the automatic control unit
are completed.
If the switch on the burner is in the OFF position, the automatic control unit will not
proceed from
Ph12:
Move the switch to the
ON
position to continue.
!
This manual describes
“0=speed standardization”
type burners.