Par
.
no.
Par
ameter
Number of
elements
T
ype
Edit
V
alue r
ange
Min Max
Reso-
lution
Default
setting
Passwor
d le
vel
126
Display brightness
1
Std_u8
edit
0%
100%
1%
LMV37.400...: 75 % LMV37.420...: 100 %
SO
128
Fuel meter: Pulse valency [pulses / volume unit]
1
Std_u16
edit
0
400
0.01
0
SO
130
Delete display of err
or history
To delete the display: Set par
ameter to 1, then to 2
Return value 0: Job successfully completed
Return value -1: Timeout of 1_2 sequence
1
Std_s8
edit
-5
2
1
0
SO
133
Default output for TÜV test
Invalid = TÜV test when output is active
2.000...10.000 = lo
w-fir
e...high-fir
e or stage 1 / stage 2 /
stage 3
1
Output
edit / clear
20 %
100 %
0.1 %
undefined
SO
141
Oper
ating mode BA
CS
0 = off
, 1 = Modbus, 2 = r
eserved
1
Selection
edit
0
2
1
0
SO
142
Setback time in the e
vent of communication br
eakdo
wn
Setting values
0 = inactive, 1….7200 s
1
Std_u16
edit
0 s
7200 s
1 s
120 s
SO (BA)
143
Reserved
1
Std_u8
edit
1
8
1
1
Info / Service
144
Reserved
1
Std_u16
edit
10 s
60 s
1 s
30 s
SO
145
De
vice addr
ess for Modbus of basic unit
Setting values
1…247
1
Std_u8
edit
1
247
1
1
SO
146
Setting of Baud r
ate for Modbus communication
Setting values: 0 = 9600, 1 = 19200
1
Selection
edit
0
1
1
1
SO
147
Parity for Modbus
0 = none, 1 = odd, 2 = e
ven
1
Selection
edit
0
2
1
0
SO
148
Default output if communication with building automation
is interrupted.
Setting values:
For
modulation oper
ation
the setting r
ange is as follo
ws:
0…19.9 = burner off
, 20…100 = 20…100% burner r
ating
For
multistage oper
ation
apply to setting r
ange:
0 = burner OFF
, P1, P2, P3
Invalid = no default output pr
edefined b
y building
automation
Default setting:
Invalid
1
Output
edit / clear
0%
100%
0.1%
undefined
SO (BA)