Par
.
no.
Par
ameter
Number of
elements
T
ype
Edit
V
alue r
ange
Min Max
Reso-
lution
Default
setting
Passwor
d le
vel
200
Basic unit
201
Burner oper
ating mode (fuel tr
ain, modulating / multistage,
actuators, etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod only gas actuator
20 = Gp1 mod only gas actuator
21 = Gp2 mod only gas actuator
22 = Lo mod only oil actuator
23 = Ho mod. sep. cir
culation
24 = Ho 2-stage sep. cir
culation
25 = Ho mod. without cir
culation
26 = Ho 2-stage without cir
culation
27 = Ho 3-stage without cir
culation
1
Selection
edit / clear
1
27
1
undefined
SO
204
Analog output invalid (4…20 mA)
0 = default load lo
w-fir
e
1 = safety shutdo
wn + start pr
evention
1
Std_u8
edit
0
1
1
1
SO
Summary of Contents for STG 146i/2