Par
.
no.
Par
ameter
Number of
elements
T
ype
Edit
V
alue r
ange
Min Max
Reso-
lution
Default
setting
Passwor
d le
vel
235
Gas: Air pr
essur
e switch (LP)
0 = inactive, 1 = active
2 = active, e
xcept phase 60...66 (pneumatic oper
ation only)
1
Selection
edit
1
2
1
1
SO
236
Gas: Pr
essur
e switch-min input
0 = inactive
1 = pr
essur
e switch-min (upstr
eam of fuel valve 1 (V1))
2 =
valve pr
oving via pr
essur
e switch-min (between fuel
valves 1 (V1) and 2 (V2))
1
Selection
edit
1
2
1
1
SO
237
Gas: Pr
essur
e switch-max / POC input
0 = inactive
1 = pr
essur
e switch-max
2 = POC
3 = pr
essur
e switch valve pr
o
ving
1
Selection
edit
1
2
1
LMV37.400...: 1 LMV37.420...: 2
SO
239
Gas: For
ced intermittent oper
ation
0 = inactive, 1 = activated
1
Selection
edit
0
1
1
1
SO
241
Gas: Ex
ecution valve pr
oving
0 = no valve pr
o
ving
1 = valve pr
o
ving on startup
2 = valve pr
o
ving on shutdo
wn
3 = valve pr
o
ving on startup and shutdo
wn
1
Selection
edit
0
3
1
LMV37.400...: 2 LMV37.420...: 0
SO
248
Gas: Postpur
ge time (t3) (abortion with load contr
oller (LR)-
ON
1
Time
edit
1 s
108 min
0.2 s
1 s
SO
400
Ratio curves
401
Ratio contr
ol curve fuel actuator (only curve settings)
13
Std_s16
edit
0°
90°
0.1°
0°; 0°; 15°; undefined
SO
402
Ratio contr
ol curve air actuator (only curve settings)
13
Std_s16
edit
0°
90°
0.1°
0°; 90°; 45°; undefined
SO
403
Ratio contr
ol curve VSD (only curve settings)
13
Std_s16
edit
15 %
100%
0.1%
0%; 100%; 50%;
undefined
SO
500
Ratio contr
ol
501
No-flame positions fuel actuator
Inde
x 0 = home position
Inde
x 1 = pr
epur
ge position
Inde
x 2 = postpur
ge position
3
Std_s16
edit
0°
90°
0.1°
Inde
x
0
1
2
Value
0°
0°
15°
SO