Par
.
no.
Par
ameter
Number of
elements
T
ype
Edit
V
alue r
ange
Min Max
Reso-
lution
Default
setting
Passwor
d le
vel
502
No-flame positions air actuator
Inde
x 0 = home position
Inde
x 1 = pr
epur
ge position
Inde
x 2 = postpur
ge position
3
Std_s16
edit
0°
90°
0.1°
Inde
x
0
1
2
Value
0°
90°
45°
SO
503
No-flame speeds VSD
Inde
x 0 = no-load speed
Inde
x 1 = pr
epur
ge speed
Inde
x 2 = postpur
ge speed
3
Std_s16
edit
0%
100%
0.1%
Inde
x
0
1
2
Value
0% 100% 50%
SO
522
Ramp up
1
Std_u8
edit
5 s
40 s
1 s
10 s
SO
523
Ramp do
wn
1
Std_u8
edit
5 s
40 s
1 s
10 s
SO
542
Activation of VSD / PWM fan
0 = inactive, 1 = active
1
Selection
edit
0
1
1
0
SO
544
Ramp modulating
1
Std_u8
edit
32 s
80 s
1 s
32 s
SO
545
Lo
wer output limit
undefined = 20 %
1
Output
edit / clear
20%
100%
0.1%
undefined
SO (BA)
546
Upper output limit
undefined = 100 %
1
Output
edit / clear
20%
100%
0.1%
undefined
SO (BA)
600
Actuators
601
Selection of r
efer
ence point
Inde
x 0 = fuel, Inde
x 1 = air
, 0 = close (<0°), 1 = open (>90°)
2
Selection
edit
0
1
1
Inde
x
0
1
Value
0
1
SO
602
Actuator
’s dir
ection of r
otation
Inde
x 0 = fuel, Inde
x 1 = air
, 0 = counter
clockwise
1 = clockwise (e
xclusively for SQM3...)
2
Selection
edit
0
1
1
Inde
x
0
1
Value
0
1
SO
606
Toler
ance limit of position monitoring [0.1°]
Inde
x 0 = fuel, Inde
x 1 = air
Gr
eatest position err
or wher
e a fault is secur
ely detected
err
or detection band: (par
ameter 606-0.6°) to
par
ameter 606
2
Std_u8
edit
0.5°
4°
0.1°
Inde
x
0
1
Value
1.7°
1.7°
SO
611
Type of r
efer
encing
Inde
x 0 = fuel, Inde
x 1 = air
, 0 = standar
d, 1 = stop within
usable r
ange, 2 = internal stop (SQN1...), 3 = both
2
Std_u8
edit
0
3
1
Inde
x
0
1
Value
0
0
SO