INSTALLATION
46
HYDRONIC UNIT B
46
Service parameters
Par
.
Jbus
Sigla
Description
Field
Default
Unit
Control panel
CCN
Table
301
INV_MODEL
Model inverter
-
RO
Inverter
302
INV_PROGRAM_
VERSION
Inverter program version
-
RO
Inverter
303
INV_PROGRAM_
REVISION
Inverter program revision
-
RO
Inverter
304
INV_EEPROM_CODE
EEPROM inverter code
-
RO
Inverter
305
INV_SWITCH_SETTING
Inverter switch setting
-
RO
Inverter
306
050BH
INV_CDU_CAP
ACITY
Capacity CDU
0÷15
-
RO
RO
Inverter
307
INV_MCU_CODE
Code MCU
-
RO
Inverter
308
INV_CDU_CURRENT
CDU corrente
mA
Inverter
311
DEF_OVERRIDE
Override defrost
-4÷24
-
Inverter
-4 = Not avaliable
-3 = Old version inverter software
-2 = Hot optimization not configured
-1 = Free defrost disabled
0 = No override
1 =
TO2 too low
2 = Conditions not met
3 = W
aiting for the first mechanical defrost
10 = Mechanical defrost not completed
11 = Forced mechanical defrost request
12 = Mechanical defrost in progress
21 = Free defrost start
22 = Free Defrost in progress
23 = Free Defrost stopped
24 = Free Defrost mode exit
312
DEF_DEL
TA_T_REF_MD
Defrost Delta
T (MD)
0.0÷30.0
K
Inverter
313
DEF_DEL
TA_T_REF
Defrost
Delta T
0.0÷30.0
K
Inverter
314
DEF_DEL
TA_T
Current defrost delta
T
K
Inverter
315
DEF_FROST_F
ACT
OR
Frosting factor
%
Inverter
316
FREE_DEFROST_NB
Free defrost cycle number
-
Inverter
317
DEFROST_DURA
TION
Free defrost duration
s
Inverter
318
TIME_SINCE_LAST_MD
Time since last MD
min
Inverter
319
TIME_SINCE_LAST_FD
Time since last FD
min
Inverter
321
QCK_ENA
QT
: Activation of the quick test mode
0÷1
-
RW/F
QCH_TEST
[No/yes]